Plan Review Notes
Plan Review Notes For Permit 19060927
Permit Number 19060927
Review Stop B
Sequence Number 2
Notes
Date Text
2019-07-05 09:24:08****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 COMMENTFROM PREVIOUS LIST:
  
 1. WHEN COMPLETING THE INSTALLATION SCHEDULE, PLEASE
 NOTE PAGE 13 OF 20, FACTORS APPLY DEPENDING ON
 SUBSTRATE, EDGE DISTANCE AND FASTENER. FOR FASTENER, IF
 USING TAPCON, BE SPECIFIC AS TO WHICH TAPCON (TAPCON
 W/ADVANCED THREADFORM TECHNOLOGY REQUIRES A .9 FACTOR).
  
 2ND REVIEW, THE .9 FACTOR WAS NOT APPLIED TO THE 12"
 ANCHOR SPACING FOR TAPCON W/ADVANCED THREDFORM
 TECHNOLOGY FASTENER.
  
 ALSO NOTE THAT ANCHOR TYPES A, D, U ARE SPECIFIED ON
 THE INSTALLATION SCHEDULE BUT A, H AND D ARE
 HIGHLIGHTED; PLEASE CORRELATE.
  
 2. YOU MAY RESUBMIT UP TO TWO PAGES, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
  
  
  