Date Text
2019-06-20 16:02:53FAILED
  
 1) ALL ELEMENTS NEED TO BE BELOW THE HEIGHT OF THE
 EIGHT (8) FOOT TALL PERIMETER FENCE:
  
 A. THE WAVEGUIDE BRIDGE IS SHOWN POSSIBLY EXCEEDING
 EIGHT FEET IN HEIGHT. PROVIDE THE EXACT HEIGHT AND
 ENSURE THAT IT IS NO TALLER THEN EIGHT FEET.
 B. NO HEIGHT INFORMATION PROVIDED ON THE CABINET
 HEIGHTS - NOTE THIS MUST INCLUDE THE SLAB HEIGHT THAT
 THEY SIT ON AND BE LESS THEN EIGHT FEET TALL.
 C. THE ELECTRICAL H-FRAME AND EVERYTHING MOUNTED TO IT
 NEEDS TO BE SHOWN AS LOWER THEN EIGHT FEET IN HEIGHT.
 D. THE TOP OF THE POLE FOR THE AMOB UNITS NEEDS TO BE
 SHOWN AT NO TALLER THEN EIGHT FEET - INCLUDING THE SLAB
 IT IS MOUNTED ON.
  
 2) THE GENERATOR REQUIRES A SEPARATE PERMIT WITH PLANS.
 PLEASE NOTE THAT YOU WILL NEED TO PROVIDE THE FULL
 HEIGHT OF THE GENERATOR, INCLUDING THE SLAB IT IS
 MOUNTED ON.
  