2019-07-12 16:21:49 | BUILDING REVIEW COMMENTS: |
| |
| W.P.B. PERMIT: 19060806 |
| REVIEWED: JULY 12, 2019 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER PX4191 |
| [email protected] |
| 561-805-6718 |
| |
| FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| FBC[EXISTING] = FBC EXISTING BUILDING |
| FBC[A] = FBC ACCESSIBILITY |
| FBC[E] = FBC ENERGY CONSERVATION |
| FBC[R] = FBC RESIDENTIAL |
| |
| 109.3 FBC[AMENDED] PROVIDE COPY OF PROPOSAL WITH |
| CONTRACTOR TO SHOW WORK VALUE EQUAL TO THE AMOUNT SHOWN |
| ON PERMIT APPLICATION, OR ADJUST VALUE TO MATCH ACTUAL |
| COST OF WORK. PLEASE ADJUST FEE AT FRONT DESK AND PAY |
| ADJUSTED PERMIT REVIEW FEE AT TIME OF RE-SUBMITTAL. |
| - ALSO, PROVIDE PROJECT DESCRIPTION IF IT IS NOT |
| INCLUDED ON THE PROPOSAL. |
| |
| 301.1 FBC[EXISTING] GENERAL. THE REPAIR, ALTERATION, |
| CHANGE OF OCCUPANCY, ADDITION OR RELOCATION OF ALL |
| EXISTING BUILDINGS SHALL COMPLY WITH ONE OF THE METHODS |
| LISTED IN SECTIONS 301.1.1 THROUGH 301.1.3 AS SELECTED |
| BY THE APPLICANT. SECTIONS 301.1.1 THROUGH 301.1.3 |
| SHALL NOT BE APPLIED IN COMBINATION WITH EACH OTHER. |
| A) 301.1.1 FBC[EXISTING] PRESCRIPTIVE COMPLIANCE |
| METHOD. REPAIRS, ALTERATIONS, ADDITIONS AND CHANGES OF |
| OCCUPANCY COMPLYING WITH CHAPTER 4 OF THIS CODE IN |
| BUILDINGS COMPLYING WITH THE FLORIDA FIRE PREVENTION |
| CODE SHALL BE CONSIDERED IN COMPLIANCE WITH THE |
| PROVISIONS OF THIS CODE. |
| B) 301.1.2 FBC[EXISTING] WORK AREA COMPLIANCE METHOD. |
| REPAIRS, ALTERATIONS, ADDITIONS, CHANGES IN OCCUPANCY |
| AND RELOCATED BUILDINGS COMPLYING WITH THE APPLICABLE |
| REQUIREMENTS OF CHAPTERS 5 THROUGH 13 OF THIS CODE |
| SHALL BE CONSIDERED IN COMPLIANCE WITH THE PROVISIONS |
| OF THIS CODE. |
| C) 301.1.3 FBC[EXISTING] PERFORMANCE COMPLIANCE METHOD. |
| REPAIRS, ALTERATIONS, ADDITIONS, CHANGES IN OCCUPANCY |
| AND RELOCATED BUILDINGS COMPLYING WITH CHAPTER 14 OF |
| THIS CODE SHALL BE CONSIDERED IN COMPLIANCE WITH THE |
| PROVISIONS OF THIS CODE. |
| - WHICH METHOD IS BEING USED FOR COMPLIANCE? |
| (PRESCRIPTIVE,WORK AREA OR PERFORMANCE). |
| |
| 501 FBC[EXISTING] STATE THE LEVEL OF ALTERATION FOR |
| WORK BEING PERFORMED IF WORK AREA COMPLIANCE METHOD IS |
| BEING USED. |
| |
| 107.5.3 FBC[AMENDED] PLEASE PROVIDE DRAWING THAT DEPICT |
| EXISTING CONDITIONS, DEMOLITION (IF APPLICABLE) AND |
| PROPOSED CHANGES. DESIGN CRITERIA, PRODUCT APPROVALS, |
| SCHEDULES AND DETAILS FOR NEW WORK. |
| NEW WORK WILL NEED TO COMPLY WITH ENERGY CODE. |
| ALSO, THE FLOOR PLAN LABELED AS-BUILT SOUNDS LIKE WORK |
| HAS BEEN PERFORMED. IS THIS WORK ALREADY COMPLETE? |
| |
| REVIEW HAS NOT BEEN PERFORMED DUE TO LACK OF |
| INFORMATION ON THE PLANS. PLEASE PROVIDE TWO SETS OF |
| PLANS THAT DEPICT THE WORK TO BE PERFORMED SO THAT A |
| REVIEW CAN BE COMPLETED ON THE SECOND REVIEW. |
| |
| NOTES: |
| -COMMENTS ARE A BRIEF OVERVIEW OF CODE SECTIONS. |
| FURTHER REVIEW OF THE REFERENCED CODE SECTIONS WILL BE |
| REQUIRED. |
| -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| OF MATERIALS REQUESTED. |
| -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| NEED "VOID", RENDERING THEM NOT USABLE. |
| |
| PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| [email protected] |
| |
| |
| |