2019-08-08 14:06:482ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19060803
 8/8/2019
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 1) THE REQUESTED AC LOAD CALCULATIONS AND ENERGY
 COMPLIANCE REPORT WERE NOT SUBMITTED- PLEASE COMPLY.
  
 2) SHEET M-2 FAN SCHEDULE NOTE 3: PROVIDE A THERMOSTAT
 TO CONTROL THE HEATER IN THE FITTING ROOM. SEE CODE
 SECTIONS BELOW.
  
 C403.2.4 HVAC SYSTEM CONTROLS.
  
 EACH HEATING AND COOLING SYSTEM SHALL BE PROVIDED WITH
 THERMOSTATIC CONTROLS AS SPECIFIED IN SECTION
 C403.2.4.1, C403.2.4.1.3, C403.2.4.2, C403.2.4.3,
 C403.3.1, C403.4, C403.4.1 OR C403.4.4.
  
 C403.2.4.1 THERMOSTATIC CONTROLS.
  
 THE SUPPLY OF HEATING AND COOLING ENERGY TO EACH ZONE
 SHALL BE CONTROLLED BY INDIVIDUAL THERMOSTATIC CONTROLS
 CAPABLE OF RESPONDING TO TEMPERATURE WITHIN THE ZONE.
 WHERE HUMIDIFICATION OR DEHUMIDIFICATION OR BOTH IS
 PROVIDED, AT LEAST ONE HUMIDITY CONTROL DEVICE SHALL BE
 PROVIDED FOR EACH HUMIDITY CONTROL SYSTEM.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  