2019-06-25 14:11:19 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| NFPA 30A |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| |
| 1ST REVIEW |
| PLUMBING COMMEMTS: DENIED |
| |
| PLEASE NOTE THAT SOME ISSUES ARE ARCHITECTURAL. THESE |
| ISSUES MUST BE SATISFACTORILY ADDRESSED PRIOR TO |
| APPROVAL OF THE PLUMBING APPLICATION FOR PERMIT. |
| 1. RE: PLAN SHEET AS101; |
| A. BUILDING CODE ANALYSIS INDICATES USE & OCCUPANCY IS |
| MERCANTILE AND STORAGE. PER WPB FBC 107.2.1, THE |
| ARCHITECT SHALL PROVIDE THE OCCUPANT LOAD FOR THE |
| BUILDING IN ACCORDANCE WITH FBC 1004.1. |
| 1) AS I SEE IT THE OCCUPANT LOAD FOR THE BUILDING |
| EXCEEDS 15 PERSONS WHICH WILL REQUIRE A DRINKING |
| FOUNTAIN AND A SERVICE SINK PER FBC PL TABLE 403.1. |
| 2. RE: PLAN SHEET AE106; |
| A. PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED IN A |
| HORIZONTAL POSITION, 33 INCHES (840 MM) MINIMUM AND 36 |
| INCHES (915 MM) MAXIMUM ABOVE THE FINISH FLOOR MEASURED |
| TO THE TOP OF THE GRIPPING SURFACE, NOT TO CENTER OF |
| THE GRIPPING SURFACE. |
| B. PER WPB FBC 107.2.1, PLEASE REMOVE ALL DETAILS THAT |
| DO NOT PERTAIN TO THE PROJECT. THIS INCLUDES, BUT IS |
| NOT LIMITED TO DETAILS FOR THE SHOWER, FLOOR MOP SINK |
| AND THE URINAL. |
| 3. RE: PLAN SHEET AE101; |
| A. RM. 102: PER FBC ACC 212.3, WHERE SINKS ARE |
| PROVIDED, AT LEAST 5 PERCENT, BUT NO FEWER THAN ONE, OF |
| EACH TYPE PROVIDED IN EACH ACCESSIBLE ROOM OR SPACE |
| SHALL COMPLY WITH 606. (PLEASE NOTE, MOP OR SERVICE |
| SINKS SHALL NOT BE REQUIRED TO COMPLY WITH 212.3.) |
| B. PER FBC ACC SECTION 606.2, PROVIDE CLEAR FLOOR SPACE |
| FOR THE SINK. |
| C.PER FBC ACC 606.3, SINK SHALL BE INSTALLED WITH THE |
| FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 |
| INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR |
| GROUND. |
| 4. RE: PLAN SHEET P-1; |
| A. THE WATER HEATER SCHEDULE CALLS FOR AN EEMAX |
| TANKLESS ELECTRIC WATER HEATER; THE WATER HEATER DETAIL |
| SHOWS THE WATER HEATER TO BE A TANK TYPE WITH STORAGE. |
| ADDITIONALLY, THERE IS AN IN-LINE HI-LO THERMOSTATIC |
| MIXING VALVE SHOWN. PER WPB FBC 107.2.1, PLEASE |
| CLARIFY. IF THE WATER HEATER DETAIL SHOWN ON THE PLAN |
| DOES NOT APPLY, THEN PLEASE REMOVE IT PER WPB FBC |
| 107.2.1. |
| B. PER WPB FBC 107.2.1, PROVIDE THE ELECTRICAL |
| CHARACTERISTICS OF THE WATER HEATER ON THE SCHEDULE. |
| C. P & T RELIEF VALVE IS CALLED OUT ON THE SCHEDULE. IS |
| THIS REQUIRED ON A TANKLESS WATER HEATER. IF IT IS, |
| THEN PER WPB FBC 107.2.1, PROVIDE A DETAIL OF THE UNIT, |
| WITH PIPING AND VALVE ARRANGEMENT, INCLUDING LOCATION |
| OF THE RELIEF VALVE AND DISCHARGE PIPING. |
| D. SEE PLUMBING FIXTURE SCHEDULE. PER FBC PL 416.5, |
| PROVIDE TEMPERING WATER DEVICE AT THE LAVATORIES |
| CONFORMING TO ASSE 1070 OR CSA B125.3. |
| E.PER FBC TABLE 403.1, PROVIDE A DRINKING FOUNTAIN AND |
| SERVICE SINK. |
| 1) PER FBC PL 410.3, REQUIRED DRINKING FOUNTAIN SHALL |
| BE A BI-LEVEL WITH TWO SPOUTS WHICH ACCOMMODATES WHEEL |
| CHAIR ACCESSIBILITY AND MEETS THE NEEDS OF STANDING |
| PEOPLE, OR TWO SEPARATE DRINKING FOUNTAINS MEETING |
| THOSE SAME REQUIREMENTS SHALL BE FURNISHED. |
| 5. PLUMBING SHEETS SIGNATURE IS BY ENGINEER AND IS |
| SELF-CERTIFIED; REQUIRES THIRD PARTY CERTIFICATION. |
| ADDITIONALLY, THERE IS A NOTE ON EACH OF THE PLUMBING |
| PLANS STATING THAT THE PLAN HAS BEEN ELECTRONICALLY |
| SIGNED AND SEALED BY JASON D. P.E. 73050 USING A SHA-1 |
| AUTHENTICATION CODE. IS THIS A LEGITIMATE CERTIFIED |
| AUTHORITY? PLEAS PROVIDE TRUSTED CERTIFICATE AUTHORITY. |
| |
| |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| PHONE 561-805-6715 |
| |
| 19060803 8225 IBIS BLVD |
| |