2019-07-09 12:14:04 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #19060803 |
| 7/9/18 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW |
| AC SYSTEM IN ACCORDANCE WITH SECTION C403.2.1 FBC EC. |
| |
| 2) SUBMIT AN ENERGY COMPLIANCE REPORT- SEE SECTIONS |
| C101.2, C101.5.1 AND C401.2 FBC EC. |
| |
| 3) SHEETS AE101 & M-3: THE "FITTING ROOM" APPEARS TO BE |
| AN OCCUPIED SPACE THAT REQUIRES EITHER NATURAL OR |
| MECHANICAL VENTILATION, AND A SPACE HEATING SYSTEM. |
| PLEASE SEE SECTIONS 401.2 & 309.1 FBC M AND SHOW |
| COMPLIANCE. |
| |
| 4) AE101 & M-3: "FITTING ROOMS" PER TABLE 403.3.1.1 FBC |
| REQUIRE EXHAUST VENTILATION AT A RATE OF 0.25 CFMS PER |
| SQ. FT. THERE IS ALSO A LARGE OVERHEAD ROLL-UP DOOR |
| THAT WOULD ALLOW VEHICLES TO ACCESS THE SPACE AND BE |
| STORED THERE. PLEASE NOTE THAT EXHAUST VENTILATION AT A |
| RATE OF 0.75 CFMS PER SQ. FT. IS REQUIRED FOR GARAGES- |
| TABLE 403.3.1.1 FBC M. PLEASE REVISE THE PLANS TO MEET |
| COMPLIANCE. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |
| CHRISTOPHER L. COLE |
| BUILDING PLANS EXAMINER |