Plan Review Notes
Plan Review Notes For Permit 19060803
Permit Number 19060803
Review Stop M
Sequence Number 1
Notes
Date Text
2019-07-09 12:14:041ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19060803
 7/9/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEM IN ACCORDANCE WITH SECTION C403.2.1 FBC EC.
  
 2) SUBMIT AN ENERGY COMPLIANCE REPORT- SEE SECTIONS
 C101.2, C101.5.1 AND C401.2 FBC EC.
  
 3) SHEETS AE101 & M-3: THE "FITTING ROOM" APPEARS TO BE
 AN OCCUPIED SPACE THAT REQUIRES EITHER NATURAL OR
 MECHANICAL VENTILATION, AND A SPACE HEATING SYSTEM.
 PLEASE SEE SECTIONS 401.2 & 309.1 FBC M AND SHOW
 COMPLIANCE.
  
 4) AE101 & M-3: "FITTING ROOMS" PER TABLE 403.3.1.1 FBC
 REQUIRE EXHAUST VENTILATION AT A RATE OF 0.25 CFMS PER
 SQ. FT. THERE IS ALSO A LARGE OVERHEAD ROLL-UP DOOR
 THAT WOULD ALLOW VEHICLES TO ACCESS THE SPACE AND BE
 STORED THERE. PLEASE NOTE THAT EXHAUST VENTILATION AT A
 RATE OF 0.75 CFMS PER SQ. FT. IS REQUIRED FOR GARAGES-
 TABLE 403.3.1.1 FBC M. PLEASE REVISE THE PLANS TO MEET
 COMPLIANCE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  