Plan Review Notes
Plan Review Notes For Permit 19060803
Permit Number 19060803
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-06-24 09:56:23THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) A WATER SUPPLY/FIRE HYDRANT COULD NOT BE IDENTIFIED
 NEAR OF AROUND THE PROPOSED BUILDING.
  
 A WATER SUPPLY IS REQUIRED.
  
 PER NFPA 1
  
 18.3 WATER SUPPLIES.
 18.3.1* AN APPROVED WATER SUPPLY CAPABLE OF SUPPLYING
 THE REQUIRED
 FIRE FLOW FOR FIRE PROTECTION SHALL BE PROVIDED TO ALL
 PREMISES UPON
 WHICH FACILITIES, BUILDINGS, OR PORTIONS OF BUILDINGS
 ARE HEREAFTER
 CONSTRUCTED OR MOVED INTO THE JURISDICTION. THE
 APPROVED WATER
 SUPPLY SHALL BE IN ACCORDANCE WITH SECTION 18.4.
  
 18.4.5.3 BUILDINGS OTHER THAN ONE- AND TWO-FAMILY
 DWELLINGS.
 18.4.5.3.1 THE MINIMUM FIRE FLOW AND FLOW DURATION FOR
 BUILDINGS OTHER THAN ONE- AND TWO-FAMILY DWELLINGS
 SHALL BE AS
 SPECIFIED IN TABLE 18.4.5.2.1.
  
 18.5 FIRE HYDRANTS.
 18.5.1 FIRE HYDRANT LOCATIONS AND DISTRIBUTION. FIRE
 HYDRANTS
 SHALL BE PROVIDED IN ACCORDANCE WITH SECTION 18.5 FOR
 ALL NEW
 BUILDINGS, OR BUILDINGS RELOCATED INTO THE JURISDICTION
 UNLESS OTHERWISE
 PERMITTED BY 18.5.1.1 OR 18.5.1.2.
  
 18.5.3 BUILDINGS OTHER THAN DETACHED ONE- AND
 TWO-FAMILY
 DWELLINGS. FIRE HYDRANTS SHALL BE PROVIDED FOR
 BUILDINGS OTHER
 THAN DETACHED ONE- AND TWO-FAMILY DWELLINGS IN
 ACCORDANCE WITH
 BOTH OF THE FOLLOWING:
 (1) THE MAXIMUM DISTANCE TO A FIRE HYDRANT FROM THE
 CLOSEST
 POINT ON THE BUILDING SHALL NOT EXCEED 400 FT (122 M).
 (2) THE MAXIMUM DISTANCE BETWEEN FIRE HYDRANTS SHALL
 NOT
 EXCEED 500 FT (152 M).
  
 PLEASE INDICATE WHERE THE CLOSET FIRE HYDRANT IS OR
 PROVIDE ONE THAT MEETS THE ABOVE NOTED CODES.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  