2019-06-22 17:41:18 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10 |
| 2. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| 3. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| SERVICE. SHOW ON PLAN. NEC 250.94 |
| 4. PROVIDE GROUNDING DETAIL SHOWING ALL GROUNDING |
| ELECTRODES PRESENT AND SIZE OF GROUNDING ELECTRODE |
| CONDUCTOR TO EACH. IF NO OTHER GROUDING ELECTRODES ARE |
| PRESENT AND THE GROUND ROD IS THE ONLY GROUNDING |
| ELECTRODE TO BE INSTALLED, PROVIDE A SUPPLEMENTAL |
| GROUNDING ELECTRODE AT LEAST 6 FEET AWAY OR PROVIDE |
| EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR LESS. |
| NEC 250.53(A)(2) |
| 5. RISER DIAGRAM SHOWS A REDUCED NEUTRAL, WIRE SIZE # |
| 8, BEING RUN TO MAIN BREAKER PANEL FROM METER CAN. IF |
| THE INTENT IS TO USE A REDUCED NEUTRAL, PROVIDE A LOAD |
| CALCULATION FOR THE NEUTRAL. IF THIS IS NOT THE INTENT |
| AND THIS WAS INCLUDED AS AN EQUIPMENT GROUNDING |
| CONDUCTOR, THEN PROVIDE CORRECTION SO THAT THERE ARE |
| FOUR #3 WIRES FOR THE 3 PHASE SERVICE AND NO EGC. THERE |
| SHOULD NOT BE AN EGC IN THIS CONDUIT. NEC 220.61, |
| 250.6, 250.24 |
| 6. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND |
| SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN |
| THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE |
| INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN |
| SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC |
| 105.1, 107.2.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |