Plan Review Notes
Plan Review Notes For Permit 19060803
Permit Number 19060803
Review Stop B
Sequence Number 1
Notes
Date Text
2019-07-09 13:04:322017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19060803- IBIS GOLF TRAINING FACILITY
 ADD: 8225 IBIS ROAD
 CONT: THE WEITZ CO.
 TEL: 561-214-1561
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JULY 09/2019
 ACTION: DENIED
  
 1) SHEET S-2 UNDER THE HEADING OF FOUNDATION INDICATES
 THERE IS A FOUNDATION INVESTIGATION REPORT PREPARED BY
 TERRACON. PLEASE PROVIDE A SIGNED AND SEALED OR
 ELECTRONIC SIGNATURE AND SEAL TO THE BUILDING
 DEPARTMENT IN COMPLIANCE WITH:
 2017 FBC-B SECTION 2017 FBC-B 1803.5.2 QUESTIONABLE
 SOIL. WHERE THE CLASSIFICATION, STRENGTH OR
 COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR WHERE A
 LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE
 PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION
 BE CONDUCTED.
  
 2) THIS REVIEW CYCLE NO ENERGY CALCULATIONS WERE
 SUBMITTED. 2017 FBC-ENERGY CODE:
 C401.2 APPLICATION.
 COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF THE
 FOLLOWING:
 1.THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1, EXCLUDING
 SECTION 9.4.1.1(G) OF THE STANDARD.
 2.THE REQUIREMENTS OF SECTIONS C402 THROUGH C405. IN
 ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY
 WITH SECTION C406 AND TENANT SPACES SHALL COMPLY WITH
 SECTION C406.1.1.
 3.THE REQUIREMENTS OF SECTIONS C402.5, C403.2, C404,
 C405.2, C405.3, C405.5, C405.6 AND C407. THE
 BUILDING ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85
 PERCENT OF THE STANDARD REFERENCE DESIGN
 BUILDING.
  
 3) SHEET S-2THE COMPONENTS AND CLADDING PRESSURES FOR
 ZONES 1,2,3,4 & 5 ARE ALL GOOD AND LISTED IN VASD.
 THANK YOU. WITH THE WIND DESIGN PRESSURES GOOD EITHER
 THE DESIGN PROFESSIONAL OR THE CONTRACTOR CAN ASK FOR
 DEFERRED SUBMITTALS FOR COMPONENTS AND CLADDING.
  
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 3A) REQUIRED PRODUCT APPROVALS FOR COMPONENTS AND
 CLADDING. 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS , OVERHEAD COILING DOORS,
 MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 3B) PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED
 OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 3C) SHEET AE-103 DETAIL # 6 SHOWS THE INSTALLATION OF A
 GALVANIZED OVERHEAD DOOR & GUIDES. THERE IS ALSO A NOTE
 THAT IF EXPANSION BOLTS ARE INSTALLED PER THE
 MANUFACTURES WRITTEN SPECIFICATION. PLEASE SUBMIT FOR
 REVIEW BY THE DESIGNER OF RECORD AND HIGHLIGHT THE
 BACKSET FROM THE EDGE OF THE CONCRETE COLUMN (SHEET
 S-1FOUNDATION NOTE 5 TC-1 COLUMN) AND THE DERATING OF
 BOLT AND THE REQUIRED SPACING TO MEET THE WIND LOAD
 PRESSURES. 107.2.1.2 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 4) SHEET AE101 SHOWS THE USE OF A DECORATIVE FOAM BAND.
 . PLEASE SHOW COMPLIANCE WITH SECTION 1408 OF THE 2017
 FBC-B EFIS. HOW WILL HE EFIS TRIM BE ANCHORED TO THE
 BUILDING SECTIONS 1408.3 AND 1408.4. 2017 FBC-B SECTION
 1408.4 WEATHER RESISTANCE. EIFS SHALL COMPLY WITH
 SECTION 1403 AND SHALL BE DESIGNED AND CONSTRUCTED TO
 RESIST WIND AND RAIN IN ACCORDANCE WITH THIS SECTION
 AND THE MANUFACTURER?S APPLICATION INSTRUCTIONS.
  
 5) PLEASE REVIEW SHEET AE102 DETAIL # 2 & 5. THE PLAN
 INDICATES THE INSTALLATION OF HIGH RIB GALVANIZED METAL
 LATH AND THE USE OF 1 INCH WOOD PURLINS TO BE ATTACHED
 TO THE BOTTOM CHORD OF THE WOOD ROOF TRUSSES. PLEASE
 REVIEW IN THE 2017 FBC-B SECTION 2511.1.1 INSTALLATION
 AND TABLE 2511.1.1 LATHING & FURRING (CEMENT PLASTER/
 STUCCO) ASTM C1063.
 5A) PLEASE NOTE THIS NOTE DOES NOT INDICATE THE
 ATTACHMENT METHOD OF THE WIRE LATH INTO THE HORIZONTAL
 PURLIN, NOR DOES THE NOTE INDICATE HOW THE PURLIN IS TO
 BE ANCHORED INTO THE BOTTOM OF THE ROOF TRUSS?
 WHEN REVIEWING ASTM C1063 IF NAILS ARE TO SECURE THE
 METAL EXPANDED 3/ 8 INCH RIB LATH THE HORIZONTAL PURLIN
 WITH EITHER NAILS OR STAPLES, NOT LESS THAN 1 ? INCH
 PENETRATION INTO THE HORIZONTAL WOOD FRAMING MEMBER.
 SEE ASTM C1063- 7.10.2.3.
  
 5B) ASTM 1063-7.10.2.5. SCREWS USED TO ATTACH METAL
 PLASTER BASE TO HORIZONTAL AND VERTICAL FRAMING MEMBERS
 SHALL PENETRATE NOT LESS THAN 5/8 INCH INTO THE MEMBER
 WHEN THE LATH IS INSTALLED AND SHALL ENGAGE NOT LESS
 THAN 3 STRANDS OF LATH. WHEN INSTALLING RIB LATH THE
 SCREWS SHALL PASS THROUGH, BUT NOT DEFORM THE RIB.
  
 5C) PLEASE ALSO NOTE THAT EACH RIB OF 3/8 INCH EXPANDED
 RIB LATH (4 INCHES ON CENTER) NEEDS TO BE ATTACHED TO
 THE WOOD FRAMING MEMBER AND TRUSSES NOT SPACED MORE
 THAN 2 FEET ON CENTER. SEE ASTM 1063-7.10.1.1.
  
 6) SHEET AE-106:
 6A) PLEASE UPDATE NOTES FOR THE HEIGHT OF THE WATER
 CLOSET GRAB BARS. AS SHOWN ON THE PLANS THEY ARE BEING
 MEASURED FROM FINISH FLOOR TO THE CENTER LINE OF THE
 BAR. PLEASE REVIEW THE 2017 FBC-ACCESSIBILITY CODE
 SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM
 AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE, NOT CENTERLINE.
  
 6B) PLEASE UPDATE THE PLAN FOR THE LOCATION THAT THE
 MIRROR OVER THE LAV IS MEASURED. ALL MIRROR FRAMES ARE
 NOT REFLECTIVE. 2017 FBC-ACCESSIBILITY CODE 603.3
 MIRRORS. MIRRORS LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
  
 7) SHEETS AE 101 CLUB REPAIR BENCH AND AE103 DETAIL 2
 INDICATE THE HEIGHT OF THE BENCH (TOP) TO BE 36 INCHES
 ABOVE FINISH FLOOR AND ALSO A STAINLESS STEEL HAND
 SINK. PLEASE REVIEW THE 2017 FBC-ACCESSIBILITY CODE
 SECTIONS:
  
 7A) 902.1 .WORK SURFACES SHALL COMPLY WITH 902.2 AND
 902.3. ADVISORY 902.1 EXAMPLES OF WORK SURFACES INCLUDE
 WRITING SURFACES, STUDY CARRELS, STUDENT LABORATORY
 STATIONS, BABY CHANGING AND OTHER TABLES OR FIXTURES
 FOR PERSONAL GROOMING, COUPON COUNTERS, AND WHERE
 COVERED BY THE ADA SCOPING PROVISIONS, EMPLOYEE WORK
 STATIONS.
  
 7B) 606 SINKS. 2017 FBC-ACCESSIBILITY CODE SECTION
 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE INSTALLED
 WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER
 SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 8) DIGITAL SUBMITTALS: PLANS WILL BE REVIEWED BY THE
 PBC IMPACT FEE OFFICE DIGITALLY VIA PROJECT DOX UPON
 NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR
 WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE
 WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY
 UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE. THE FORM CAN BE FOUND AT:
 HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  