Plan Review Notes For Permit 19060794 |
Permit Number |
19060794 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-06-24 13:05:20 | PLUMBNG 1ST REVIEW**DENIED** | | | | 1) PLANS SHALL BE WET SIGNED AND SEALED BY PERSON | | DESIGNING PLANS. FS 471, 481 | | | | 2) R405-2017 FORM CALL OUT GAS TANKLESS HWH WITH AN EF | | OF .80. THE MIN FEDERAL STANDARD IS .82 E.F PLEASE | | REFER TO FEDERAL REGISTER/ VOL 81, NO 250 | | | | 3) SHT E-1 UNDER PANEL SCHUDULE CALLS OUT THE WATER | | HEATER AS STORAGE TYPE 4500 WATT BUT R405-2017 FORM | | CALLS OUT GAS TANKLESS. PLEASE CLARIFY AND SUPPLIE | | MANUFACTURES INSTALLATION MANUAL. FBC 107.2.1 | | | | 4) PROVIDE A SANITARY RISER / ISOMETRIC DRAWING OF THE | | PLUMBING SYSTEM. FBC 107.3.5 | | | | 5) PROVIDE SHOWER PAN DETAIL SHOWER MATERIAL BEING USED | | AND 2% PRE-SLOPE. FBC 107.2.1 | | | | TIM HUNT | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | CITY OF WEST PALM BEACH | | 561-248-2703 | | [email protected] | | [email protected] | | |
|