Plan Review Notes
Plan Review Notes For Permit 19060794
Permit Number 19060794
Review Stop P
Sequence Number 1
Notes
Date Text
2019-06-24 13:05:20PLUMBNG 1ST REVIEW**DENIED**
  
 1) PLANS SHALL BE WET SIGNED AND SEALED BY PERSON
 DESIGNING PLANS. FS 471, 481
  
 2) R405-2017 FORM CALL OUT GAS TANKLESS HWH WITH AN EF
 OF .80. THE MIN FEDERAL STANDARD IS .82 E.F PLEASE
 REFER TO FEDERAL REGISTER/ VOL 81, NO 250
  
 3) SHT E-1 UNDER PANEL SCHUDULE CALLS OUT THE WATER
 HEATER AS STORAGE TYPE 4500 WATT BUT R405-2017 FORM
 CALLS OUT GAS TANKLESS. PLEASE CLARIFY AND SUPPLIE
 MANUFACTURES INSTALLATION MANUAL. FBC 107.2.1
  
 4) PROVIDE A SANITARY RISER / ISOMETRIC DRAWING OF THE
 PLUMBING SYSTEM. FBC 107.3.5
  
 5) PROVIDE SHOWER PAN DETAIL SHOWER MATERIAL BEING USED
 AND 2% PRE-SLOPE. FBC 107.2.1
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR