Plan Review Notes
Plan Review Notes For Permit 19060794
Permit Number 19060794
Review Stop B
Sequence Number 1
Notes
Date Text
2019-07-15 13:00:57BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19060794
 REVIEWED: JULY 15, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1) FL STATUTE 481.221(2)?SEALS; DISPLAY OF CERTIFICATE
 NUMBER
 - ARCHITECT OF RECORD NEEDS TO SIGN AND SEAL THE
 DRAWINGS.
  
 2) 107.5.3 FBC[AMENDED] UPDATE CODE EDITION TO STATE
 CURRENT VERSIONS.
 - SHEET A-3 STATES CODE VERSION AS 2014. PLEASE UPDATE
 TO CURRENT VERSION FLORIDA BUILDING CODE(FBC), 6TH
 EDITION (2017).
  
 3) 301.1 FBC[EXISTING] GENERAL. THE REPAIR, ALTERATION,
 CHANGE OF OCCUPANCY, ADDITION OR RELOCATION OF ALL
 EXISTING BUILDINGS SHALL COMPLY WITH ONE OF THE METHODS
 LISTED IN SECTIONS 301.1.1 THROUGH 301.1.3 AS SELECTED
 BY THE APPLICANT. SECTIONS 301.1.1 THROUGH 301.1.3
 SHALL NOT BE APPLIED IN COMBINATION WITH EACH OTHER.
 A) 301.1.1 FBC[EXISTING] PRESCRIPTIVE COMPLIANCE
 METHOD. REPAIRS, ALTERATIONS, ADDITIONS AND CHANGES OF
 OCCUPANCY COMPLYING WITH CHAPTER 4 OF THIS CODE IN
 BUILDINGS COMPLYING WITH THE FLORIDA FIRE PREVENTION
 CODE SHALL BE CONSIDERED IN COMPLIANCE WITH THE
 PROVISIONS OF THIS CODE.
 B) 301.1.2 FBC[EXISTING] WORK AREA COMPLIANCE METHOD.
 REPAIRS, ALTERATIONS, ADDITIONS, CHANGES IN OCCUPANCY
 AND RELOCATED BUILDINGS COMPLYING WITH THE APPLICABLE
 REQUIREMENTS OF CHAPTERS 5 THROUGH 13 OF THIS CODE
 SHALL BE CONSIDERED IN COMPLIANCE WITH THE PROVISIONS
 OF THIS CODE.
 C) 301.1.3 FBC[EXISTING] PERFORMANCE COMPLIANCE METHOD.
 REPAIRS, ALTERATIONS, ADDITIONS, CHANGES IN OCCUPANCY
 AND RELOCATED BUILDINGS COMPLYING WITH CHAPTER 14 OF
 THIS CODE SHALL BE CONSIDERED IN COMPLIANCE WITH THE
 PROVISIONS OF THIS CODE.
 - WHICH METHOD IS BEING USED FOR COMPLIANCE?
 (PRESCRIPTIVE,WORK AREA OR PERFORMANCE)
  
 5) 501 FBC[EXISTING] IF WORK AREA COMPLIANCE METHOD IS
 BEING USED, PLEASE ADD LEVEL OF ALTERATION TO DESIGN
 DATA.
  
 6) 103.1.1.2 FBC[RE] THE BUILDINGS OWNER, THE OWNERS
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNATED
 BY THE OWNER SHALL CERTIFY THAT THE BUILDING IS IN
 COMPLIANCE WITH THE CODE, AS PER SECTION 553.907,
 FLORIDA STATUTES, PRIOR TO RECEIVING THE PERMIT TO
 BEGIN CONSTRUCTION OR RENOVATION. 553.907, FLORIDA
 STATUTES.
 - PLEASE HAVE THE OWNER SIGN THE ENERGY CALCULATIONS.
  
 7) [FBC AMENDED 107.3.5.3.1] PLEASE PROVIDE THE ENTIRE
 APPRAISAL TO ESTABLISH IF SUBSTANTIAL APPROVMENT.
 - I'M LOOKING FOR THE APPRAISAL TO STATE MARKET VALUE
 INSTEAD ON REPLACEMENT COST.
  
 8) 107.3.5 FBC[AMENDED] PLEASE PROVIDE PROJECT DATA
 SUCH AS AREA UNDER AIR AND COVERED AREAS.
  
 9) HOW ARE CEILING TRAYS BEING CREATED?
 - PLEASE PROVIDE TRUSS ENGINEERING, OR INDICATE THAT IT
 WILL BE DEFERRED SUBMITTAL.
  
 10) 311.3 FBC[R] FLOORS AND LANDINGS AT EXTERIOR DOORS.
 THERE SHALL BE A LANDING OR FLOOR ON EACH SIDE OF EACH
 EXTERIOR DOOR. THE WIDTH OF EACH LANDING SHALL BE NOT
 LESS THAN THE DOOR SERVED. EVERY LANDING SHALL HAVE A
 DIMENSION OF NOT LESS THAN 36 INCHES (914 MM) MEASURED
 IN THE DIRECTION OF TRAVEL. THE SLOPE AT EXTERIOR
 LANDINGS SHALL NOT EXCEED 1/4 UNIT VERTICAL IN 12 UNITS
 HORIZONTAL (2 PERCENT).
 - PROVIDE LANDING AT EXTERIOR SIDE OF DOOR (FROM FAMILY
 ROOM) IF GREATER THAN 2 RISERS PROVIDED.
  
 11) 107.5.3 FBC[AMENDED] PLEASE PROVIDE IN-FILL
 DETAIL(S) FOR FILLING IN OF WINDOW, SIDELIGHTS AND
 DOOR.
  
 12) 807.1 FBC[R] ATTIC ACCESS. BUILDINGS WITH
 COMBUSTIBLE CEILING OR ROOF CONSTRUCTION SHALL HAVE AN
 ATTIC ACCESS OPENING TO ATTIC AREAS THAT HAVE A
 VERTICAL HEIGHT OF 30 INCHES (762 MM) OR GREATER OVER
 AN AREA OF NOT LESS THAN 30 SQUARE FEET (2.8 M2). THE
 VERTICAL HEIGHT SHALL BE MEASURED FROM THE TOP OF THE
 CEILING FRAMING MEMBERS TO THE UNDERSIDE OF THE ROOF
 FRAMING MEMBERS.
 - PLEASE SHOW EXISTING ATTIC ACCESSES ON FLOOR PLANS.
  
 13) 107.3.4.1 FBC[AMENDED] ARE THERE ANY TRANSOMS, IF
 YES PROVIDE PRODUCT APPROVAL (2 COPIES)
 - ALSO, THERE IS A WINDOW SCHEDULE WITH DESIGNATIONS ON
 SHEET A-2, BUT THE DESIGNATIONS ARE NOT PLACED ON PLAN
 OR ELEVATION DRAWINGS TO SHOW WHERE THEY ARE BEING
 INSTALLED. PLEASE SHOW DESIGNATIONS AND SHOW WINDOWS IN
 END ZONE IF APPLICABLE.
  
 14) 301.2(2) TABLE FBC[R]
 EXPOSURE CATEGORY = ___
 HOW WAS EXPOSURE C DETERMINED WHEN THE PROPERTY IS
 SITUATED ALONG THE INTERCOASTAL WATERWAY? PLEASE REVIEW
 THE CRITERIA OF D EXPOSURE AND UPDATE AS NEEDED.
  
 NOTES:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  