2019-06-26 13:13:40 | 06/26/2019 1ST PLUMBING/POOL REVIEW **DENIED** WITH |
| COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. SUBMIT SPECIFICATION AND SHOW ON DOCUMENTATION THAT |
| THE GAS POOL HEATER MEETS THE MINIMUM REQUIRED |
| EFFICIENCY AS REQUIRED BY THE 2017 FBC-ENERGY |
| SEC.R403.10.4. ALL GAS AND SPA HEATERS SHALL HAVE A |
| MINIMUM THERMAL EFFICIENCY OF 82 % FOR HEATERS |
| MANUFACTURED ON OR AFTER APRIL 16, 2013, WHEN TESTED IN |
| ACCORDANCE WITH ANSI Z 21.56. |
| 2. BACKFLOW PREVENTER REQUIRED PER THE CITY OF WEST |
| PALM BEACH ORD #2853-95. A PERMIT REQUIRED BY A |
| LICENSED CONTRACTOR AND MUST BE CERTIFIED BY UTILITIES |
| PRIOR TO FINAL INSPECTION. A RPZ IS REQUIRED AT METER |
| AND A PVB REQUIRED FOR POOL FILL. PLEASE ADD NOTES ON |
| PLANS AND IF OR BY OTHER! |
| 3. ON GENERAL NOTES ITEM 15 IS REFERRING TO 5TH EDITION |
| 2014, PLEASE CHANGE TO CURRENT CODE, WPB AMEND. TO FBC |
| SEC. 107.2.1. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |