Plan Review Notes
Plan Review Notes For Permit 19060791
Permit Number 19060791
Review Stop P
Sequence Number 1
Notes
Date Text
2019-06-26 13:13:4006/26/2019 1ST PLUMBING/POOL REVIEW **DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SUBMIT SPECIFICATION AND SHOW ON DOCUMENTATION THAT
 THE GAS POOL HEATER MEETS THE MINIMUM REQUIRED
 EFFICIENCY AS REQUIRED BY THE 2017 FBC-ENERGY
 SEC.R403.10.4. ALL GAS AND SPA HEATERS SHALL HAVE A
 MINIMUM THERMAL EFFICIENCY OF 82 % FOR HEATERS
 MANUFACTURED ON OR AFTER APRIL 16, 2013, WHEN TESTED IN
 ACCORDANCE WITH ANSI Z 21.56.
 2. BACKFLOW PREVENTER REQUIRED PER THE CITY OF WEST
 PALM BEACH ORD #2853-95. A PERMIT REQUIRED BY A
 LICENSED CONTRACTOR AND MUST BE CERTIFIED BY UTILITIES
 PRIOR TO FINAL INSPECTION. A RPZ IS REQUIRED AT METER
 AND A PVB REQUIRED FOR POOL FILL. PLEASE ADD NOTES ON
 PLANS AND IF OR BY OTHER!
 3. ON GENERAL NOTES ITEM 15 IS REFERRING TO 5TH EDITION
 2014, PLEASE CHANGE TO CURRENT CODE, WPB AMEND. TO FBC
 SEC. 107.2.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  