Plan Review Notes
Plan Review Notes For Permit 19060712
Permit Number 19060712
Review Stop B
Sequence Number 1
Notes
Date Text
2019-06-24 16:17:30BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19060712
 REVIEWED: JUNE 24, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[E] = FBC ENERGY CONSERVATION
  
 1) 301.2.1.1 FBC[R] WIND DESIGN CRITERIA
 RISK CATEGORY = ___(II)
 EXPOSURE CATEGORY = ___(B,C OR D)
 BUILDING CLASSIFICATION = __________(ENCLOSED)
 MEAN BLDG. HGT. = ___FT. ___IN.(THIS WILL BE THE HEIGHT
 MEASURED FROM THE GROUND TO IN BETWEEN EAVE AND ROOF
 PEAK)
 WIND SPEED V ULT = _____(170)
 WIND SPEED V ASD = _____(132)
 -PLEASE ADD WIND DESIGN CRITERIA TO COVER SHEET.
  
 2) PLEASE PROVIDE ON ADDITIONAL COPY OF EACH PRODUCT
 APPROVAL. EACH PERMIT NEEDS 2 SETS OF PRODUCT APPROVALS
 AND BETWEEN THE TWO PERMITS I WAS ONLY ABLE TO FIND
 ENOUGH FOR ONE SET EACH.
 17-0630.01, 17-0411.06, 17-0614.11 AND FL-15210.1
  
 3) THE WINDOW MARKS ON SHEET A1 AND A2 DON?T MATCH THE
 MARKS ON COVER. -PLEASE SHOW MARKS ON COVER TO MATCH SO
 ONLY COVER GETS REVISED.
 ALSO, MARK EGRESS ON HORIZONTAL SLIDER IF THAT IS
 INTENDED FOR BEDROOM EMERGENCY ESCAPE.
  
 4) 310.1 FBC[R] UNITS 409W AND 409E HAVE NO EMERGENCY
 ESCAPE AND NO OPERABLE WINDOWS. THIS IS TECHNICALLY A
 SLEEPING ROOM AND SHOULD HAVE A WINDOW FOR EMERGENCY
 EGRESS. ALSO, THERE WOULD BE NO NATURAL VENTILATION
 PROVIDED.
  
 5) R303.3 BATHROOMS. BATHROOMS, WATER CLOSET
 COMPARTMENTS AND OTHER SIMILAR ROOMS SHALL BE PROVIDED
 WITH AGGREGATE GLAZING AREA IN WINDOWS OF NOT LESS THAN
 3 SQUARE FEET (0.3 M2), ONE-HALF OF WHICH MUST BE
 OPENABLE.
 EXCEPTION: THE GLAZED AREAS SHALL NOT BE REQUIRED WHERE
 ARTIFICIAL LIGHT AND A LOCAL EXHAUST SYSTEM ARE
 PROVIDED. THE MINIMUM LOCAL EXHAUST RATES SHALL BE
 DETERMINED IN ACCORDANCE WITH SECTION M1507. EXHAUST
 AIR FROM THE SPACE SHALL BE EXHAUSTED DIRECTLY TO THE
 OUTDOORS
 HOW ARE BATHROOMS (ALL UNITS) VENTILATED?
 -SHOW MECHANICAL VENTILATION IF FIXED WINDOWS ARE BEING
 USED.
  
 NOTES:
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved