Date |
Text |
2019-06-24 16:17:30 | BUILDING REVIEW COMMENTS: |
| |
| W.P.B. PERMIT: 19060712 |
| REVIEWED: JUNE 24, 2019 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER PX4191 |
| [email protected] |
| 561-805-6718 |
| |
| FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| FBC[B] = FBC BUILDING |
| FBC[EXISTING] = FBC EXISTING BUILDING |
| FBC[E] = FBC ENERGY CONSERVATION |
| |
| 1) 301.2.1.1 FBC[R] WIND DESIGN CRITERIA |
| RISK CATEGORY = ___(II) |
| EXPOSURE CATEGORY = ___(B,C OR D) |
| BUILDING CLASSIFICATION = __________(ENCLOSED) |
| MEAN BLDG. HGT. = ___FT. ___IN.(THIS WILL BE THE HEIGHT |
| MEASURED FROM THE GROUND TO IN BETWEEN EAVE AND ROOF |
| PEAK) |
| WIND SPEED V ULT = _____(170) |
| WIND SPEED V ASD = _____(132) |
| -PLEASE ADD WIND DESIGN CRITERIA TO COVER SHEET. |
| |
| 2) PLEASE PROVIDE ON ADDITIONAL COPY OF EACH PRODUCT |
| APPROVAL. EACH PERMIT NEEDS 2 SETS OF PRODUCT APPROVALS |
| AND BETWEEN THE TWO PERMITS I WAS ONLY ABLE TO FIND |
| ENOUGH FOR ONE SET EACH. |
| 17-0630.01, 17-0411.06, 17-0614.11 AND FL-15210.1 |
| |
| 3) THE WINDOW MARKS ON SHEET A1 AND A2 DON?T MATCH THE |
| MARKS ON COVER. -PLEASE SHOW MARKS ON COVER TO MATCH SO |
| ONLY COVER GETS REVISED. |
| ALSO, MARK EGRESS ON HORIZONTAL SLIDER IF THAT IS |
| INTENDED FOR BEDROOM EMERGENCY ESCAPE. |
| |
| 4) 310.1 FBC[R] UNITS 409W AND 409E HAVE NO EMERGENCY |
| ESCAPE AND NO OPERABLE WINDOWS. THIS IS TECHNICALLY A |
| SLEEPING ROOM AND SHOULD HAVE A WINDOW FOR EMERGENCY |
| EGRESS. ALSO, THERE WOULD BE NO NATURAL VENTILATION |
| PROVIDED. |
| |
| 5) R303.3 BATHROOMS. BATHROOMS, WATER CLOSET |
| COMPARTMENTS AND OTHER SIMILAR ROOMS SHALL BE PROVIDED |
| WITH AGGREGATE GLAZING AREA IN WINDOWS OF NOT LESS THAN |
| 3 SQUARE FEET (0.3 M2), ONE-HALF OF WHICH MUST BE |
| OPENABLE. |
| EXCEPTION: THE GLAZED AREAS SHALL NOT BE REQUIRED WHERE |
| ARTIFICIAL LIGHT AND A LOCAL EXHAUST SYSTEM ARE |
| PROVIDED. THE MINIMUM LOCAL EXHAUST RATES SHALL BE |
| DETERMINED IN ACCORDANCE WITH SECTION M1507. EXHAUST |
| AIR FROM THE SPACE SHALL BE EXHAUSTED DIRECTLY TO THE |
| OUTDOORS |
| HOW ARE BATHROOMS (ALL UNITS) VENTILATED? |
| -SHOW MECHANICAL VENTILATION IF FIXED WINDOWS ARE BEING |
| USED. |
| |
| NOTES: |
| |
| -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| NEED "VOID", RENDERING THEM NOT USABLE. |
| |
| PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| [email protected] |
| |
| |
| |