Plan Review Notes
Plan Review Notes For Permit 19060697
Permit Number 19060697
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-06-21 13:42:35THE FOLLOWING COMMENTS WERE SUBMITTED BY SANDRA THOMAS,
 FIRE INVESTIGATOR, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 1. A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE
 COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION
 SUBMITTED ON THE PLANS.
  
 2. NO ADDRESS PROVIDED ON THE PLAN TITLEBLOCK.
  
 3. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 4. PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 5.PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY
 TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS,
 EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF
 TRAVEL ETC.
  
 6.WHAT IS CURRENT OCCUPANCY TYPE, AND WHAT WILL THE
 PROPOSED OCCUPANCY BE AFTER RENOVATION?
  
 7. ALL LIFE SAFETY ASPECTS OF THE PROPOSED PROJECT
 SHALL COMPLY WITH THE CURRENT EDITION OF THE 2015
 FLORIDA FIRE PREVENTION CODE AND ALL APPLICABLE CODES
 CONTAINED THEREIN. 1. BUILDING PLANS, FLOOR PLANS,
 ELEVATIONS AND/OR DETAILED DRAWINGS WERE NOT CONTAINED
 IN THE SUBMITTAL AND CANNOT BE COMMENTED ON.
  
 8.THE LIFE SAFETY SYSTEMS, SPRINKLER AND/OR FIRE ALARM,
 SHALL REMAIN ACTIVE THROUGHOUT THE CONSTRUCTION PERIOD.
  
 9.ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 10.PROVIDE DRAWING NOTE INDICATING, FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 S. THOMAS
 561-804-4728