Plan Review Notes
Plan Review Notes For Permit 19060680
Permit Number 19060680
Review Stop B
Sequence Number 2
Notes
Date Text
2019-06-25 17:24:14RESIDENTIAL (R3) RE-ROOF, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 1- RAS 117 CALCULATIONS DONE BY TERRENCE E. LUNN NEED
 TO BE REVISED. ACCORDING TO SEC. R301.2.1.4
 FBC-RESIDENTIAL THIS BUILDING IS LOCATED IN EXPOSURE
 "C" NOT EXPOSURE "B". REVISE AS REQUIRED OR PROVIDE
 ENGINEERING ANALYSIS AS ALLOWED BY THE EXCEPTION OF
 SEC. R301.2.1.4 FBC-RESIDENTIAL.
  
 RESPONSE:
 A) REVISED RAS 117 CALCULATIONS DON'T HAVE AN ORIGINAL
 ENGINEER'S SEAL AND SIGNATURE AS REQUIRED BY CHAPTER
 471 F.S. WHEN SUBMITTING CALCULATIONS/DOCUMENTS FOR
 PUBLIC RECORDS. CALCULATIONS SUBMITTED SHOW WHAT LOOKS
 LIKE A COPY OF THE ENGINEER'S SEAL AND SIGNATURE. NEED
 ORIGINALS.
  
 B) IT LOOKS LIKE THERE IS A TYPO ON THE REVISED
 CALCULATIONS SUBMITTED. THE FIRST PARAGRAPH OF LETTER
 SUBMITTED STATES EXPOSURE CATEGORY C BUT SECOND
 PARAGRAPH STATES EXPOSURE CATEGORY B. REVISE AS
 REQUIRED TO MATCH. SEC. R301.2.1.4 FBC-RESIDENTIAL AND
 SEC. 107.2.1 CITY AMENDMENTS.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved