2019-06-14 18:27:15RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 SEC. 801.3 FBC-EXISTING BUILDING.
  
 1- RAS 117 CALCULATIONS DONE BY TERRENCE E. LUNN NEED
 TO BE REVISED. ACCORDING TO SEC. R301.2.1.4
 FBC-RESIDENTIAL THIS BUILDING IS LOCATED IN EXPOSURE
 "C" NOT EXPOSURE "B". REVISE AS REQUIRED OR PROVIDE
 ENGINEERING ANALYSIS AS ALLOWED BY THE EXCEPTION OF
 SEC. R301.2.1.4 FBC-RESIDENTIAL.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  