Plan Review Notes
Plan Review Notes For Permit 19060669
Permit Number 19060669
Review Stop P
Sequence Number 1
Notes
Date Text
2019-06-18 08:48:35PLUMBING 1ST REVIEW**DENIED**
  
 1) VALUE APPEARS LOW. PROVIDE A SIGNED BONA FIDE
 CONTRACT. WPB AMEND 109.3
  
 2) THIS BUILDINBG WAS BUILT IN 2007 UNDER THE FAIR
 HOUSING ACT (FHA). ALL FHA ELEMENTS SHALL REMAIN.
 PROVIDE CABINET HEIGHT DETAIL SHOWING THE NEW VANITIES
 WILL COMPLY WITH MAX BEING 34". FHA 7.52
  
 3) UNDER YOUR SCOPE OF WORK YOU REFER TO BTHROOM'S AND
 A NEW SHOWER PAN BUT ONLY 1 BATHRROM IS SHOWN ON THE
 FLOOR PLAN AND NO SHOWER. PLEASE CLARIFY. FBC 107.2.1
  
 4) PROVIDE SHOWER PAN DETAIL SHOWER WHAT MATERIAL IS
 BEING USED AND FLOORING WITH BE PRE-PITCHED 2%. FBC
 107.2.1
  
 5) PLANS SHALL BE SIGNED BY PERSON TAKING
 RESPONSIBILITY. FS 471, 481, 489
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  
  