2019-06-18 12:48:10 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM |
| (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561) |
| 805-6724 |
| [email protected] |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| RESULTS: DENIED |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. FBC B 107.2.1, PROVIDE DRAWING DETAIL SHOWING |
| CONSTRUCTION METHOD OF NEW SHOWER WALLS IN COMPLIANCE |
| WITH R307.2 & R702.4.2. |
| 2. FBC B 107.2.1, PROVIDE A CROSS SECTION DETAIL |
| SHOWING CONSTRUCTION METHOD OF NEW SHOWER FLOOR. |
| 3. CLARIFY IF REPLACING TILE ON BATHROOM FLOORS AND |
| PROVIDE TEST REPORTS THAT DEMONSTRATE COMPLIANCE WITH |
| THE SECTIONS BELOW; |
| FBC B 603.1 FLAME SPREAD; INSULATION BETWEEN A FINISHED |
| FLOOR AND SOLID DECKING W/O AN INTERVENING SPACE |
| W/FLAME SPREAD INDEX OF 200 OR LESS. |
| FBC B 804 ? FLOORING |
| FBC B 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E |
| FBC B 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |