2019-07-22 15:19:12 | BUILDING REVIEW COMMENTS: |
| |
| W.P.B. PERMIT: 19060662 |
| REVIEWED: JULY 22, 2019 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER PX4191 |
| [email protected] |
| 561-805-6718 |
| |
| FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| FBC[EXISTING] = FBC EXISTING BUILDING |
| FBC[A] = FBC ACCESSIBILITY |
| FBC[E] = FBC ENERGY CONSERVATION |
| |
| 1) 107.5.3 FBC[AMENDED] UPDATE CODE EDITION TO STATE |
| CURRENT VERSIONS. |
| - PLEASE UPDATE SHEET A-002 AT BOTTOM FOR WINDOWS AND |
| DOORS TO COMPLY WITH FBC 2017 6TH EDITION. |
| |
| 2) 501.1.1 FBC[RE] ADDITIONS, ALTERATIONS, OR REPAIRS: |
| GENERAL. ADDITIONS, ALTERATIONS, OR REPAIRS TO AN |
| EXISTING BUILDING, BUILDING SYSTEM OR PORTION THEREOF |
| SHALL COMPLY WITH SECTION R502, R503 OR R504. UNALTERED |
| PORTIONS OF THE EXISTING BUILDING OR BUILDING SUPPLY |
| SYSTEM SHALL NOT BE REQUIRED TO COMPLY WITH THIS CODE. |
| - EXEMPTION IN NOTES ON SHEET A-100 FOR 30% STRUCTURE |
| VALUE IS NO LONGER IN THE ENERGY CODE. SECTION 501.1.1 |
| DOES APPLIES. PLEASE REMOVE NOTE ABOUT EXEMPTION. |
| |
| 3) 503.1.1 FBC[E] BUILDING ENVELOPE ASSEMBLIES THAT ARE |
| PART OF THE ALTERATION SHALL COMPLY WITH SECTION |
| R402.1.2 OR R402.1.4, SECTIONS R402.2.1 THROUGH |
| R402.2.13, R402.3.1, R402.3.2, R402.4.3 AND R402.4.5 |
| - CHOOSE METHOD FOR COMPLIACE AND SHOW HOW PLANS MEET. |
| I'M MAINLY LOOKING FOR INSULATION VALUES AT ROOF AND |
| WALLS OF NEWLY ENCLOSED SPACE. |
| |
| 4) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR |
| WINDOWS AND DOOR. |
| |
| |