2019-06-18 09:08:08GAS PROVISO:
  
 408.4SEDIMENT TRAP.
 WHERE A SEDIMENT TRAP IS NOT INCORPORATED AS PART OF
 THE APPLIANCE, A SEDIMENT TRAP SHALL BE INSTALLED
 DOWNSTREAM OF THE APPLIANCE SHUTOFF VALVE AS CLOSE TO
 THE INLET OF THE APPLIANCE AS PRACTICAL. THE SEDIMENT
 TRAP SHALL BE EITHER A TEE FITTING HAVING A CAPPED
 NIPPLE OF ANY LENGTH INSTALLED VERTICALLY IN THE
 BOTTOMMOST OPENING OF THE TEE AS ILLUSTRATED IN FIGURE
 408.4 OR OTHER DEVICE APPROVED AS AN EFFECTIVE SEDIMENT
 TRAP. ILLUMINATING APPLIANCES, RANGES, CLOTHES DRYERS,
 DECORATIVE VENTED APPLIANCES FOR INSTALLATION IN VENTED
 FIREPLACES, GAS FIREPLACES AND OUTDOOR GRILLS NEED NOT
 BE SO EQUIPPED.
  
 410.2MP REGULATORS.
 MP PRESSURE REGULATORS SHALL COMPLY WITH THE FOLLOWING:
 WHERE CONNECTED TO RIGID PIPING, A UNION SHALL BE
 INSTALLED WITHIN 1 FOOT (304 MM) OF EITHER SIDE OF THE
 MP REGULATOR.
  