2019-07-16 13:40:07 | FAILED |
| |
| PROVIDE WRITTEN RESPONSE TO COMMENTS. |
| |
| 1) SOME POLE LOCATIONS HAVE CHANGED FROM THE CITY |
| COMMISSION APPROVED PLANS. THE NEW LOCATIONS ARE |
| REQUIRED TO BE SHOWN ON AS BUILT PLAN AMENDMENTS |
| REQUIRED FOR THIS PROJECT. |
| |
| 2) THE PHOTOMETRIC PLANS PROVIDED WITH THE PLANS SHOW |
| LIGHTING LEVELS WHICH EXCEED THE STANDARDS LISTED IN |
| SECTION 94-113(B) "ALL BUILDINGS SHALL PROVIDE EXTERIOR |
| LIGHTING EVERY NIGHT FROM DUSK TO DAWN TO ILLUMINATE |
| BUILDING ENTRANCES, ADJACENT SIDEWALKS, AND PATHS, AT A |
| MINIMUM OF 0.6 FOOTCANDLES AS MEASURED AT THE BACK EDGE |
| OF THE CURB AND ONE FOOT ABOVE THE SIDEWALK. THIS |
| MEASUREMENT SHALL INCLUDE LIGHT EMANATING FROM PUBLIC |
| AND PRIVATE SOURCES. UNSHIELDED LIGHT FIXTURES SHALL BE |
| PROHIBITED. THE MAXIMUM MEASURE SHALL BE NO MORE THAN |
| 1.0 FOOTCANDLE." STAFF RECOGNIZES THAT THE FDOT STREET |
| LIGHTS MAY EXCEED THE 1.0 FOOTCANDLE MAXIMUM, SO PLEASE |
| PLEASE PROVIDE VERIFICATION THAT YOUR PROPOSED LIGHTS |
| DO INDEPENDENTLY COMPLY WITH THE STANDARDS. |
| |
| 3) PLEASE PROVIDE INFORMATION TO CONFIRM THE FRONTAGE |
| ALONG TAMARIND AVENUE AND IRIS STREET COMPLIES WITH THE |
| MINIMUM 0.6 FOOTCANDLE REQUIRED AT CURB ONE FOOT ABOVE |
| GRADE. LIGHTING LEVEL CAN BE FROM PRIVATE AND PUBLIC |
| SOURCE. |
| |
| 4) PROPOSED LIGHTING ALONG SAPODILLA AVENUE AND IRIS |
| STREET SHALL BE THE SAME HEIGHT OF EXISTING LIGHTING |
| ALONG ROSEMARY AVENUE IN CITYPLACE. |
| |
| 5) PROPOSED LIGHTING ALONG OKEECHOBEE BLVD SHALL BE THE |
| SAME HEIGHT OF PROPOSED LIGHTING AT INTERSECTION OF |
| ROSEMARY AVE AND OKEECHOBEE BLVD. PLEASE CONTACT UYEN |
| DANG 494-1040 (1087) FOR DETAILS. |
| |
| CONTACT ERIC SCHNEIDER @ (561) 822-1446 - |
| [email protected] OR ANA MARIA APONTE @ (561) 822-1439 |
| - [email protected] |
| |