Plan Review Notes
Plan Review Notes For Permit 19060596
Permit Number 19060596
Review Stop E
Sequence Number 2
Notes
Date Text
2019-07-15 09:58:37FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
  
 INVERTER 32A X 125% = 40A + 150 = 190A 150A X 120% =
 180A
  
  
 705.12(D)(3)(B) WHERE TWO SOURCES, ONE A UTILITY AND
 THE OTHER AN
 INVERTER, ARE LOCATED AT OPPOSITE ENDS OF A BUSBAR THAT
 CONTAINS
 LOADS, THE SUM OF 125 PERCENT OF THE INVERTER(S) OUTPUT
 CIRCUIT
 CURRENT AND THE RATING OF THE OVERCURRENT DEVICE
 PROTECTING THE
 BUSBAR SHALL NOT EXCEED 120 PERCENT OF THE AMPACITY OF
 THE
 BUSBAR. THE BUSBAR SHALL BE SIZED FOR THE LOADS
 CONNECTED IN
 ACCORDANCE WITH ARTICLE 220. A PERMANENT WARNING LABEL
 SHALL
 BE APPLIED TO THE DISTRIBUTION EQUIPMENT ADJACENT TO
 THE BACKFED
 BREAKER FROM THE INVERTER THAT DISPLAYS THE FOLLOWING
 OR
 EQUIVALENT WORDING: