Plan Review Notes For Permit 19060578 |
Permit Number |
19060578 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-06-17 07:26:48 | GAS 1ST REVIEW**DENIED** | | | | 1) GENERATOR PERMIT APP # 19051389 HAS THE GENERATOR AS | | 890,000 BTU'S. YOUR PLAN IS ONLY CALLING OUT 600,000 | | BTU'S. PLEASE CLARIFY | | | | 2) PROVIDE INSTALLATION MANUAL FOR THE GAS STOVE. | | SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / | | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY | | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND 2017 | | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED | | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS | | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF | | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. | | | | 3) VALUE IS TOO LOW. VALUE MUST INCLUDE THE COST OF | | BOTH TANKLESS WAETR HEATER, GAS STOVE, PIPE, MATERIALS, | | LABOR, OVERHEAD, AND PROFITS. PROVIDE A SIGNED BONA | | FIDE CONTRACT. WPB AMEND 109.3. | | | | | | TIM HUNT | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | CITY OF WEST PALM BEACH | | 561-248-2703 | | [email protected] | | [email protected] | | | | | | |
|