2019-07-08 17:02:11 | FLORIDA BUILDING CODE 2017 6TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| NFPA 70 2014 EDITION |
| |
| JAKE LEAHY |
| ELECTRICAL PLANS EXAMINER II |
| 561-805-6713 |
| [email protected] |
| |
| NO ELECTRIC SHOWN |
| |
| SHOW BRANCH CIRCUIT NUMBERS AND LOCATION OF PANEL, SIZE |
| OF CIRCUIT AND COMPLIANCE WITH THE FBC ENERGY |
| CONSERVATION CODE |
| |
| VALUE FOR THE SIGNS(MENU) TO LOW MUST INCLUDE ALL |
| MATERIALS AND ALL LABOR. CONTRACTOR OR CUSTOMER |
| SUPPLIED. |
| |
| FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING |
| PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| TOTAL REPLACEMENT |
| VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, |
| MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK, |
| ARCHITECTURAL AND DESIGN FEES, |
| MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| INTERNATIONAL CODE |
| CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE SET |
| BY THE BUILDING OFFICIAL. |
| |
| EXTERIOR LIGHTING CONTROLS. LIGHTING NOT DESIGNATED FOR |
| DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A |
| COMBINATION |
| OF A PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL |
| TIME SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN |
| OPERATION SHALL |
| BE CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR |
| PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF |
| RETAINING PROGRAMMING |
| AND THE TIME SETTING DURING LOSS OF POWER FOR A PERIOD |
| OF AT LEAST 10 HOURS. FBC CE 405.2.4 |