Plan Review Notes For Permit 19060342 |
Permit Number |
19060342 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-06-10 17:11:29 | GAS 1ST REVISION REVIEW**DENIED** | | | | 1) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE | | LENGTH OF ALL CUT SECTIONS OF PIPE PER R 2017 FBC-RES | | SEC. G2413.4.1, G2413.4.2. | | | | 2) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES | | USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE | | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM | | THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE | | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-RES. | | SEC. G2413.3, G2412.8, G2413.1, G2413.2, & G2413.3. | | | | 3) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM | | ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3 | | THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3. | | | | 4) THE MOUNTING MIN DISTANCE PERMITTED FOR THE TANKLESS | | WATER HEATER FROM A DOOR OR WINDOW IS 4'. PLEASE REFER | | TO PAGE 8 THE THE INSTALLATION MANUAL. FBC 107.2.1 | | | | | | TIM HUNT | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | CITY OF WEST PALM BEACH | | 561-248-2703 | | [email protected] | | [email protected] | | | | | | | | | | | | | | |
|