2019-06-10 13:33:22 | PLUMBING 1ST REVIEW**DENIED**UNABLE TO PROVIDE A |
| COMPLETE AND THOROUGH REVIEW UNTIL A COMPLETE PLAN IS |
| SUBMITTED AND ALL OF THE 1ST REVIEW COMMENTS ARE MEET. |
| |
| 1) VALUE APPEARS LOW. VALUE SHALL INCLUDE THE COST OF |
| THE TANKLESS, WASHING MACHINE, AND DRYER. 109.3 |
| BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF THE |
| BUILDING OFFICIAL, THE CLAIMED VALUATIONOF BUILDING, |
| ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR |
| PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE |
| APPLICATION, THE PERMIT SHALL BE DENIED, UNLESS THE |
| APPLICANT CAN SHOW DETAILED, QUANTITY ESTIMATES, AND/OR |
| BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO |
| MEET THE APPROVAL OF THE BUILDING OFFICIAL. FOR |
| PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS |
| SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| LAND VALUE |
| |
| 2) PERMIT APPLICATION AND YOUR PROPOSAL CALL OUT NEW |
| 1/2 BATHROOM BUT DOES NOT SHOW ON PLUMBING ISOMETRIC. |
| PROVIDE A COMPLETE DIMENSIONAL FLOOR PLAN TO INCLUDE |
| PLB, GAS, ELC, MECH IS REQUIRED. FBC 107.3.5 |
| |
| 3) PROVIDE TANKLESS GAS WATER HEATER INSTALLATION |
| MANUAL. SEE GAS COMMENTS. FBC 107.3.5 |
| |
| UNABLE TO PROVIDE A COMPLETE AND THOROUGH REVIEW UNTIL |
| A COMPLETE PLAN IS SUBMITTED AND ALL OF THE 1ST REVIEW |
| COMMENTS ARE MEET. |
| |
| |