| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. NO PLAN SUBMITTED. DOCUMENTS SUPPLIED DO NOT EXPLAIN |
| THE NATURE OF THE REPAIR. HOW LONG WILL THIS REPAIR |
| TAKE AND WHAT DOES IT ENTAIL? PERMIT APPLICATION STATES |
| THIS IS A REPAIR ON A 400 AMP BREAKER, BUT THE |
| INFORMATION SUBMITTED SEEMS TO INDICATE THIS REPAIR IS |
| ON A 4000 AMP BREAKER. CLARIFICATION NEEDED. PROVIDE |
| MORE INFORMATION. WPB FBC 107.2.1 |
| 2. PROVIDE METHOD OF COMPLIANCE WITH NEC 517.30(G). AN |
| ENGINEER WILL BE REQUIRED TO VERIFY COMPLIANCE. NEC |
| 517.30(G); FS 471.003(2)(H) |
| 3. HOW WILL TWO SOURCES OF POWER BE MAINTAINED FOR THIS |
| REPAIR? NEC 517.35 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |
| 561-805-6746 |
| [email protected] |
| |