2019-06-11 15:52:44 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. THIS BUILDING IS A TYPE 1 BUILDING, ROMEX IS NOT |
| PERMITTED. PROVIDE CORRECTION. NEC 334.12(A)(1), 334.10 |
| 2. THE FAN SPECIFIED COULD NOT BE FOUND ON THE COMPANY |
| WEBSITE. FOR THE COMPARABLE MODELS LISTED, THE RV125, |
| RV150, AND RV200, THE SPEC SHEETS DO NOT SHOW THIS |
| BEING SUPPLIED WITH A CORD. ADDITIONALLY, A CORD AND |
| RECEPTACLE ABOVE A FIXED CEILING IS NOT PERMITTED PER |
| CODE. A FIXED WIRING METHOD WITH A DISCONNECT WITHIN |
| SIGHT WILL BE REQUIRED. PROVIDE CORRECTION. NEC 400.8, |
| 422.30 |
| 3. SPEC SHEET FOR THE ABOVE MENTIONED MODELS STATES |
| THAT THE FAN MUST BE MOUNTED IN VERTICAL POSITION. THE |
| SUBMITTED PLAN SHOWS THE FAN MOUNTED HORIZONTALLY. |
| PROVIDE CLARIFICATION OR CORRECTIONS AS NEEDED. PROVIDE |
| INSTALLATION INSTRUCTIONS FOR RV100. NEC 110.3; WPB FBC |
| 107.2.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |
| 561-805-6746 |
| [email protected] |
| |