Plan Review Notes
Plan Review Notes For Permit 19060234
Permit Number 19060234
Review Stop P
Sequence Number 1
Notes
Date Text
2019-06-17 15:28:36PLUMBING 1ST REVIEW**DENIED**
  
 1) WILKINS 720A IS NOT A LEAD FREE BACKFLOW DEVICE. PER
 FEDERAL LAW AND THE CITY OF WEST PALM BEACH CROSS
 CONNECTION MANUAL (2017) ALL BACKFLOWS ARE REQUIRED TO
 BE LEAD FREE. SUBMIT A BACKFLOW THAT IS LEAD FREE AND
 MEETS BOTH FEDERAL AND CITY OF WEST PALM BEACH
 STANDARD'S.
  
  