Plan Review Notes
Plan Review Notes For Permit 19060208
Permit Number 19060208
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-06-07 13:55:25THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS NO ADDRESS NOR SUITE NUMBER ON THE
 SUBMITTED DRAWINGS.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND
 SPECIFICATIONS TO ENSURE COMPLIANCE WITH APPLICABLE
 CODES AND
 STANDARDS.
  
 PLEASE PROVIDE THE ADDRESS AND SUITE NUMBER ON EACH
 PLAN SHEET FOR CALRIFICATION AND IDENTIFICATION
 PURPOESE.
  
  
  
 2) THERE ARE NO INDICATIONS OF A FIRE ALARM OR FIRE
 SPRINKLER SYSTEM.
  
 PER NFPA 1
  
 1.14.2 THE APPLICANT SHALL BE RESPONSIBLE TO ENSURE
 THAT THE FOLLOWING CONDITIONS ARE MET:
 (1) THE CONSTRUCTION DOCUMENTS INCLUDE ALL OF THE FIRE
 PROTECTION REQUIREMENTS.
 (2) THE SHOP DRAWINGS ARE CORRECT AND IN COMPLIANCE
 WITH THE APPLICABLE CODES AND STANDARDS.
 (3) THE CONTRACTOR MAINTAINS AN APPROVED SET OF
 CONSTRUCTION DOCUMENTS ON SITE.
  
  
 PLEASE PROVIDE APPLICABLE DETAILS AND A NOTE STATING
 ALL WORK ON THESE SYSTEMS SHALL BE DONE UNDER SEPARATE
 SHOP DRAWINGS.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  