Plan Review Notes
Plan Review Notes For Permit 19060130
Permit Number 19060130
Review Stop B
Sequence Number 2
Notes
Date Text
2019-07-03 10:45:48****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FROM PREVIOUS LIST:
  
 4. NON IMPACT PRODUCT APPROVAL WAS SUBMITTED. IMPACT
 PROTECTION IS REQUIRED, FBC B 1609.1.2. IF REMOVABLE
 IMPACT PROTECTION IS PROPOSED, APPROVAL BY THE BUILDING
 OFFICIAL IS REQUIRED. IF IMPACT GLASS OR NON-REMOVABLE
 SHUTTERS ARE NOT PROPOSED, PLEASE SEND ME AN EMAIL
 PRIOR TO RESUBMITTING.
  
 THE FLORIDA STATE PRODUCT APPROVAL WAS SUBMITTED (HAS
 BOTH IMPACT AND NON IMPACT OPTIONS), BUT THE
 INSTALLATION INSTRUCTIONS AND EVALUATION REPORT
 UPLOADED PREVIOUSLY IS FOR NON IMPACT GLASS. IMPACT
 PROTECTION IS REQUIRED. IMPACT GLASS IS GENERALLY
 REQUIRED FOR COMMERCIAL AND MULTI FAMILY.
  
  
  
  