Plan Review Notes For Permit 19060130 |
Permit Number |
19060130 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2019-07-03 10:45:48 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | FROM PREVIOUS LIST: | | | | 4. NON IMPACT PRODUCT APPROVAL WAS SUBMITTED. IMPACT | | PROTECTION IS REQUIRED, FBC B 1609.1.2. IF REMOVABLE | | IMPACT PROTECTION IS PROPOSED, APPROVAL BY THE BUILDING | | OFFICIAL IS REQUIRED. IF IMPACT GLASS OR NON-REMOVABLE | | SHUTTERS ARE NOT PROPOSED, PLEASE SEND ME AN EMAIL | | PRIOR TO RESUBMITTING. | | | | THE FLORIDA STATE PRODUCT APPROVAL WAS SUBMITTED (HAS | | BOTH IMPACT AND NON IMPACT OPTIONS), BUT THE | | INSTALLATION INSTRUCTIONS AND EVALUATION REPORT | | UPLOADED PREVIOUSLY IS FOR NON IMPACT GLASS. IMPACT | | PROTECTION IS REQUIRED. IMPACT GLASS IS GENERALLY | | REQUIRED FOR COMMERCIAL AND MULTI FAMILY. | | | | | | | | |
|