Plan Review Notes For Permit 19060130 |
Permit Number |
19060130 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-06-24 10:59:25 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. FBC 107, THE FLOOR PLAN PROVIDED IS A PHOTOGRAPH. | | PROVIDE A SCANNED DOCUMENT AS THIS IS DIFFICULT TO | | READ. | | | | 2. FBC 107, PROVIDE A FLOOR PLAN WHICH HAS ALL TEXT | | ORIENTED IN THE SAME DIRECTION AS THIS IS DIFFICULT TO | | READ. | | | | 3. FBC B 1609, PROVIDE THE FLORIDA STATE PRODUCT | | APPROVAL COVER SHEET. | | | | 4. NON IMPACT PRODUCT APPROVAL WAS SUBMITTED. IMPACT | | PROTECTION IS REQUIRED, FBC B 1609.1.2. IF REMOVABLE | | IMPACT PROTECTION IS PROPOSED, APPROVAL BY THE BUILDING | | OFFICIAL IS REQUIRED. IF IMPACT GLASS OR NON-REMOVABLE | | SHUTTERS ARE NOT PROPOSED, PLEASE SEND ME AN EMAIL | | PRIOR TO RESUBMITTING. | | | | |
|