Date |
Text |
2019-06-06 13:20:08 | PERMIT 19060082 AT&T POLE 1100 BLOCK BANYAN - PBC32_874 |
| |
| PLEASE SEE THE LIST BELOW FOR AN ANALYSIS OF THE |
| DEFICIENCIES IN INFORMATION REQUIRED BY SECTION 78-401 |
| OF THE CITY OF WEST PALM BEACH CODE AS PART OF THE |
| COMMUNICATION FACILITIES PLACEMENT PERMIT APPLICATION. |
| THE DEFICIENT INFORMATION MUST BE PROVIDED FOR STAFF TO |
| REVIEW THE PERMIT APPLICATION. PLEASE NOTE THAT STAFF |
| HAS ALSO INCLUDED SOME SUBSTANTIVE REVIEW COMMENTS, |
| THAT WHILE NOT RESULTING IN A DEFICIENT APPLICATION, |
| NEED TO BE ADDRESSED OR THE PERMIT WILL NOT BE |
| APPROVED. |
| |
| 1) ENGINEERING PLANS |
| |
| A. THE ENGINEERING PLAN WAS SUBMITTED AT A 1 INCH = 100 |
| FOOT SCALE, WHICH DOES NOT COMPLY WITH THE CITY CODE |
| SCALE REQUIREMENT OF 10FT, 20FT, OR 40FT SCALE. PROVIDE |
| THE PLANS AT THE REQUIRED SCALE. |
| |
| B. THE 1100 BLOCK OF BANYAN BOULEVARD IS APPROVED FOR |
| RECONSTRUCTION. THE ENGINEERING PLANS THAT YOU |
| SUBMITTED DO NOT SHOW THE PROPOSED CONSTRUCTION |
| CONDITIONS AND THUS DO NOT ACCURATELY SHOW THE |
| PLACEMENT LOCATION FOR THE PROPOSED FACILITY. PROVIDE |
| ACCURATE PLANS BASED ON THE PROPOSED RECONSTRUCTION OF |
| THE BANYAN BOULEVARD RIGHT-OF-WAY. |
| |
| C. THE NOTES LIST ON PAGE 2 OF 20 INCORRECTLY LISTS |
| PALM BEACH COUNTY AS THE OVERSEEING AUTHORITY FOR |
| DAMAGE. BANYAN BOULEVARD IS A CITY OF WEST PALM BEACH |
| RIGHT-OF-WAY. |
| |
| 2) SURVEY OF UNDERGROUND FACILITIES - THE BASE OF THE |
| POLE IS BEING INSTALLED UNDERGROUND SO THIS IS |
| REQUIRED. |
| |
| A. AS PREVIOUSLY STATED, BANYAN BOULEVARD IS BEING |
| RECONSTRUCTED, INCLUDING UNDERGROUND UTILITY WORK AND |
| SOIL CELLS TO PROVIDE ROOT GROWTH FOR THE TREES BEING |
| INSTALLED AS PART OF THE PROJECT. ONCE THE |
| RECONSTRUCTION IS COMPLETED, PROVIDE A SURVEY SHOWING |
| ALL UNDERGROUND UTILITIES AND FEATURES, SUCH AS THE |
| SOIL CELLS, WITH THE PROPOSED POLE NOT INTERFERING WITH |
| UNDERGROUND FACILITIES OR THE TREE ROOT ZONE. |
| |
| B. THE ENGINEERING PLAN MUST BE BASED OFF OF THIS |
| SURVEY INFORMATION. |
| |
| 3) SURVEY OF ABOVEGROUND FACILITIES - A NEW POLE IS |
| BEING INSTALLED ABOVEGROUND SO THIS IS REQUIRED. |
| |
| A. AS PREVIOUSLY STATED, BANYAN BOULEVARD IS BEING |
| RECONSTRUCTED. ONCE THE RECONSTRUCTION IS COMPLETED, |
| PROVIDE A SURVEY SHOWING ALL ABOVEGROUND FEATURES, |
| INCLUDING TREES, WITH THE PROPOSED POLE NOT INTERFERING |
| WITH THE ABOVE GROUND FACULTIES, INCLUDING TREES. |
| |
| B. THE SURVEY NEEDS TO PROVIDE THE SIZE OF THE PROPOSED |
| SUPPORT STRUCTURE (POLE) BASE DIAMETER. |
| |
| C. IDENTIFY ALL ABOVEGROUND COMMUNICATION FACILITIES |
| WITHIN 50 FEET OF THE PROPOSED ANTENNA - APPLICATION |
| ONLY STATES THAT NO OTHER AT&T NETWORK POLES ARE IN THE |
| AREA, BUT FAILS TO ADDRESS OTHER COMMUNICATION |
| FACILITIES. SHOW THIS INFORMATION ON THE PLANS AND |
| PROVIDE A NARRATIVE. IF THERE ARE NO FACILITIES, THIS |
| SHALL BE NOTED ON THE SURVEY. |
| |
| D. YOU ARE REQUIRED TO PROVIDE INFORMATION REGARDING |
| EXISTING UTILITY POLES (INCLUDING LIGHT POLES) WITHIN |
| 50 FEET OF YOUR PROPOSED POLE. THE POLE HEIGHT AND BASE |
| DIAMETER SHALL BE INCLUDED. |
| |
| E. PLEASE NOTE THAT THE OVERALL LIGHT POLE HEIGHT FOR |
| THE BANYAN BOULEVARD PROJECT IS APPROXIMATELY 25 FEET. |
| THEY POLE YOU ARE PROPOSING IS 27 FEET TALL (ABOVE |
| GRADE), WHICH IS TALLER, SO IT DOES NOT MEET THE CITY |
| CODE REQUIREMENT. |
| |
| F. THE ENGINEERING PLAN MUST BE BASED OFF OF THIS |
| SURVEY INFORMATION. |
| |
| 4) CONCEALMENT METHODS DESCRIPTIONS - NO CONCEALMENT |
| INFORMATION WAS PROVIDED. PLEASE NOTE THAT ATTACHING |
| THE METER SOCKET AND POWER PANEL TO THE EXTERIOR OF THE |
| POLE DOES NOT MEET THE CITY CONCEALMENT STANDARDS |
| OUTLINED IN SECTION 78-411 OF THE CITY CODE. PROVIDE |
| REVISED PLANS AND NARRATIVE ON HOW THE INSTALLATION |
| COMPLIES WITH THE CITY'S CONCEALMENT REQUIREMENT. |
| |
| 5) RESTORATION ESTIMATE - YOU MUST PROVIDE A |
| RESTORATION ESTIMATE FOR THE SPECIFIC LOCATION OF THE |
| POLE, NOT A GENERIC ESTIMATE THAT IS NOT LINKED TO THE |
| SPECIFIC LOCATION AND WORK TO BE DONE. |
| |
| 6) RADIO FREQUENCY INTERFERENCE - NO INFORMATION WAS |
| PROVIDED THAT THE PROPOSED FACILITIES WILL NOT CAUSE |
| RADIO FREQUENCY INTERFERENCE WITH THE CITY'S PUBLIC |
| SAFETY COMMUNICATIONS EQUIPMENT. PROVIDE A STATEMENT |
| REGARDING RADIO FREQUENCY INTERFERENCE. |
| |
| 7) EVIDENCE OF INSURANCE COVERAGE |
| |
| A. THE PROVIDED CERTIFICATE OF LIABILITY INSURANCE IS |
| FROM DRAFTPROS, LLC DBA: DRAFTPROS, INC. SINCE THE |
| COMMUNICATIONS FACILITIES PLACEMENT PERMIT APPLICATION |
| LISTS NEW CINGULAR WIRELESS PCS, LLC AS THE REGISTRANT, |
| THIS IS WHOSE CERTIFICATE OF LIABILITY INSURANCE NEEDS |
| TO BE PROVIDED. |
| |
| B. PLEASE REMEMBER THAT THE CERTIFICATE OF LIABILITY |
| INSURANCE NEEDS TO NAME THE CITY OF WEST PALM BEACH, |
| ITS COMMISSIONERS, OFFICERS, EMPLOYEES AND AGENTS AS |
| ADDITIONAL INSURED AS WELL AS CHECK THE "ADDITIONAL |
| INSURED" COLUMN. |
| |
| C. ONCE THE CORRECT CERTIFICATE OF LIABILITY INSURANCE |
| HAS BEEN SUBMITTED, THE CITY'S RISK MANAGEMENT |
| DEPARTMENT WILL REVIEW TO ENSURE THAT IT COMPLIES WITH |
| CITY POLICY. |
| |
| 8) PUBLIC UTILITY LETTERS, TELEPHONE, NATURAL GAS, |
| ELECTRIC SERVICE, AND TELEVISION CABLE - THE PUBLIC |
| UTILITY LETTERS FROM THE AT&T, COMCAST, AND FPU WERE |
| NOT PROVIDED. PROVIDE COPIES OF THESE PUBLIC UTILITY |
| LETTERS. |
| |
| 9) ELECTRONIC FORMAT OF SUBMITTAL - ONLY THE PLANS WERE |
| PROVIDED IN ELECTRONIC FORM. A COPY OF ALL OF THE |
| SUBMITTAL MATERIAL MUST BE SUBMITTED IN ELECTRONIC |
| FORMAT. |
| |
| CONTACT ERIC SCHNEIDER @ (561) 822-1446 |
| [email protected] |
| |