2019-06-06 07:29:22GAS 1ST REVIEW**DENIED**
  
 1.LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU
 LOAD ON THE SYSTEM. REFER TO THE OR 2017 FBC-RES. SEC.
 G2413.3, G2413.4 AND TABLES G2413.4 (1 ) THROUGH
 G2413.4 (21). YOUR MISSING THE GAS WATER HEATER AS CITY
 RECORDS (#04070990) SHOW EXIST.
  
 2- VALUE. THE VALUE IS LOW AND MUST INCLUDE THE COST OF
 THE BBQ EVEN WHEN SUPPLIED BY OWNER. WPB AMEND 109.3.
  
 3-SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR BBQ GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  