2019-06-14 15:32:45 | ADDRESS: 2814 N FLAGLER DR PERMIT # 19060060 |
| TYPE: BLD-RES NFIP |
| |
| BUILDING PLAN REVIEW |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| BUILDING PLANS EXAMINER, PX3169 |
| 1&2 FAMILY PLANS EXAMINER, SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| RESULTS: DENIED |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| POST CONSTRUCTION ELEVATION CERTIFICATE. |
| |
| 1. THERE ARE DESCREPENCIES BETWEEN THE ELEVATIONS |
| BETWEEN THE PRE-CONSTRUCTION AND POST CONSTRUCTION |
| ELEVATION CERTIFICATES. |
| |
| 2. DESIGN PROFESSIONAL SHALL ESTABLISH ONE CONVERSION |
| FACTOR FOR EACH ELEMENTS ELEVATION. |
| |
| EX: C2(A) POST CONSTRUCTION ELEVATION IS 6.6 FEET |
| NAVD1988. PRE-CONSTRUCTION ELEVATION IS 8.0 FEET NGVD |
| 1929. THIS RESULTS IN A CONVERSION FACTOR OF 1.4. |
| C2(E) POST CONSTRUCTION ELEVATION IS 7.0 FEET NAVD |
| 1988. PRE-CONSTRUCTION ELEVATION IS 8.0 FEET NGVD 1929. |
| THIS RESULTS IN A CONVERSION FACTOR OF 1.0. |
| |
| PLEASE REVIEW ALL ELEVATIONS ON THE CERTIFICATE AND |
| RE-SUBMIT. |
| |
| NOTE: USING A FLOOD INSURANCE RATE MAP (FIRM) TO |
| ESTABLISH THE BASE FLOOD ELEVATION (BFE) CAN RESULT IN |
| A .9 FOOT RANGE IN ELEVATION. FIRM'S ROUND UP FROM |
| .5FEET AND ROUND DOWN FROM .4 FEET. |
| THE MOST ACCURATE WAY OF ESTABLISHING THE BASE FLOOD |
| ELEVATION IS TO EXTRAPOLATE THE ELEVATION BETWEEN TWO |
| TRANSECT LINES ON A FLOOD INSURANCE STUDY PROFILE. |
| (FIS). |
| EITHER METHOD MAY BE USED BUT DESIGNER NEEDS TO BE |
| AWARE OF THE POTENTIAL DESCREPANCIES IN ELEVATIONS. |
| |
| |