Plan Review Notes For Permit 19060058 |
Permit Number |
19060058 |
|
Review Stop |
SIGNATURE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-06-17 15:55:28 | ****CORRECTIONS**** | | ****REVISED 6/21**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | MEP PAGES DIGITAL SIGNATURES ARE SELF-SIGNED | | CERTIFICATES AND LACK 3RD PARTY VERIFICATION, | | FAC61G15-23.004(2)(B). PLEASE PROVIDE 3RD PARTY ISSUED | | DIGITAL SIGNATURES FOR ENGINEER ON PAGES THAT ARE | | RESUBMITTED DUE TO CODE COMMENTS OR DESIGN CHANGES. | | ALSO INCLUDE THE LANGUAGE REQUIRED FOR DIGITALLY SIGNED | | PLANS AND A SEAL (SEAL IMAGE OR STATEMENT "SIGNED AND | | SEALED" OK). | | | | | | | | | | | | | | | | | | | 2019-06-13 15:09:18 | ELECTRICAL PLANS HAVE A DIGITAL SIGNATURE, BUT THE | | DIGITAL SIGNATURE DOES NOT INCLUDE THE STATEMENT | | "SIGNED AND SEALED" AS PER FAC 61G15-23.004. THE | | SIGNATURE ONLY STATES THAT IT IS SIGNED. PROVIDE | | CORRECTION. WPB FBC 107.2.1 | | | | | 2019-06-13 09:19:43 | MECHANICAL SHEETS ARE ELECTRONICALLY SIGNED BUT NOT | | SEALED- SECTION 61G1523.005 FAC. |
|