Plan Review Notes For Permit 19060037 |
Permit Number |
19060037 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2019-07-15 10:02:32 | ***CORRECTIONS*** | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 3RD BUILDING REVIEW DENIED: | | | | FBC B 107. THE SUBMITTED PRODUCT APPROVALS DO NOT | | PROVIDE AN ENHANCED FASTENING PATTERN FOR THE ANCHORING | | OF THE BASE SHEET AT CORNER AND PERIMETER AREAS. | | | | THE ANCHOR SPACING PROVIDED IN THE PRODUCT APPROVALS | | (12" O.C.) APPEARS TO BE FOR THE FIELD SECTIONS OF | | ROOF. | | | | PLEASE PROVIDE AN ENHANCED BASE SHEET ANCHOR SPACING | | FOR AREA PRESSURES (CORNER -95.7) AND (PERIMETER | | -63.6). | | |
|