2020-01-27 05:54:401) 3RD REQUEST - THE PLANS INDICATE AN EXISTING GAS
 METER AND CITY RECORDS SHOW AN EXISTING GAS SYSTEM FOR
 THIS ADDRESS. THE BTU LOAD OF THE EXISTING GAS SYSTEM
 MUST BE ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO
 ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. IF
 UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO
 ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING
 RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING
 APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE
 SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN
 A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO
 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE
 EXISTING APPLIANCES. FGC SECS. 401.4, 401.8, 402.1,
 402.2, 402.3.
 NOTE:I PUT A COPY OF THE ORIGINAL GAS PLAN IN THE
 PERMIT APPLICATION PACKAGE AFTER THE LAST REVIEW TO BE
 GIVEN TO THE CONTRACTOR TO USE AS A REFERENCE FOR THE
 EXISTING GAS LOAD. PLEASE USE THIS DRAWING TO COMPLY
 WITH THE PLAN REVIEW COMMENTS.
 2)THE ORIGINAL GAS PLAN ON FILE IN CITY RECORDS SHOW A
 DEVELOPED LENGTH OF 158 FEET BUT THE SUBMITTED PLAN
 SHOWS A DEVELOPED LENGTH OF 20 FEET. CLARIFY. THE 158
 SHALL BE USED TO SIZE THIS SYSTEM. 2017 FBC-FUEL GAS
 SEC. 402.4.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  