Plan Review Notes
Plan Review Notes For Permit 19060025
Permit Number 19060025
Review Stop G
Sequence Number 2
Notes
Date Text
2019-12-11 05:25:421) INDICATE ON THE PLAN THE TYPE OF PIPING TO BE USED
 ABOVEGROUND AND SHOW THE REQUIRED LISTED GAS SHUTOFF
 VALVE FOR THE GENERATOR.. WPB AMEND. TO FBC SEC.
 107.2.1.
 2) A UNION IS REWUIRED WITHIN ONE FOOT UPSTREAM OR
 DOWNSTREAM OF THE REGULATOR. 2017 FBC-FUEL GAS SEC.
 410.2 (7) .
 3) A LISTED SHUTOFF VALVE IS REQUIRED IMMEDIATELY AHEAD
 OF THE REGULATOR. 2017 FBC-FUEL GAS SEC.409.4.
 4) - -2ND REQUEST - THE PLANS INDICATE AN EXISTING GAS
 METER AND CITY RECORDS SHOW AN EXISTING GAS SYSTEM FOR
 THIS ADDRESS. THE BTU LOAD OF THE EXISTING GAS SYSTEM
 MUST BE ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO
 ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. IF
 UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO
 ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING
 RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING
 APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE
 SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN
 A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO
 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE
 EXISTING APPLIANCES. FGC SECS. 401.4, 401.8, 402.1,
 402.2, 402.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW