2019-06-06 14:36:15GAS 1ST REVIEW**DENIED**
  
 1) VALUE IS TOO LOW. COST MUST INCLUDED GENERATOR EVERN
 WHEN FURNISHED BY OWNER. PERMIT # 17080950 CALLED OUT
 FOR A FURTURE 50KW THIS UNIT IS 100KW. PROVIDE BONA
 FIDE SIGN CONTRACT TO INCLUDE THE COST OF THE GENERATOR
 AND GAS PIPING THAT WILL NEED TO BE DONE TO FUEL THE
 UNIT. WPB AMEND 109.3
  
 2) PROVIDE A COMPLETE GAS PLAN. CITY RECORDS DO NOT
 SHOW ANY GAS SYSTEM ON SITE. FBC 107.3.5
  