2019-06-27 13:27:44 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) IT APPEARS THAT THE FUEL SUPPY IS NATURAL GAS. |
| |
| THERE ARE NO NATURAL GAS LINS INDICATED. A SEPARATE |
| PERMIT IS REQUIRED FOR THE NATURAL GAS LINES INCULDING |
| EQUIPEMT SPECIFICATIONS. |
| |
| PLEASE SHOW THE PROPOSED NATURAL GAS LINES ON THE SITE |
| PLAN AND PROVIDE A NOTE STATING UNDER SEPARATE PERMIT. |
| |
| |
| |
| 2) THERE IS SITE PLAN SHOWING THE SPECIFIC LOCATION OF |
| THE GENERATOR INCLUDING ALL DIMENSIONS TO AREA |
| BUILDINGS, INCLUDING NEIGHBORING PROPERTIES, AND WINDOW |
| AND DOOR AND OTHER OPENINGS. |
| |
| PER NFPA 110 |
| |
| 7.2.2 OUTDOOR EPS INSTALLATIONS. |
| 7.2.2.1 THE EPS SHALL BE INSTALLED IN A SUITABLE |
| ENCLOSURE LOCATED |
| OUTSIDE THE BUILDING AND CAPABLE OF RESISTING THE |
| ENTRANCE |
| OF SNOW OR RAIN AT A MAXIMUM WIND VELOCITY AS REQUIRED |
| BY LOCAL BUILDING CODES. |
| |
| PLEASE PROVIDE SPECIFIC SITE PLAN DETAILS. |
| |
| |
| |
| 3) THERE IS NO INDICATION OF GENERATOR CLASSIFICATION |
| NOR TYPE PER NFPA 110 |
| |
| PER NFPA 110 |
| |
| CHAPTER 4 CLASSIFICATION OF EMERGENCY POWER SUPPLY |
| SYSTEMS (EPSSS) |
| 4.1* GENERAL. THE EPSS SHALL PROVIDE A SOURCE OF |
| ELECTRICAL |
| POWER OF REQUIRED CAPACITY, RELIABILITY, AND QUALITY TO |
| LOADS FOR |
| A LENGTH OF TIME AS SPECIFIED IN TABLE 4.1(A) AND |
| WITHIN A SPECIFIED |
| TIME FOLLOWING LOSS OR FAILURE OF THE NORMAL POWER |
| SUPPLY |
| AS SPECIFIED IN TABLE 4.1(B). |
| 4.2* CLASS. THE CLASS DEFINES THE MINIMUM TIME, IN |
| HOURS, FOR |
| WHICH THE EPSS IS DESIGNED TO OPERATE AT ITS RATED LOAD |
| WITHOUT |
| BEING REFUELED OR RECHARGED. [SEE TABLE 4.1(A).] |
| 4.3 TYPE. THE TYPE DEFINES THE MAXIMUM TIME, IN |
| SECONDS, |
| THAT THE EPSS WILL PERMIT THE LOAD TERMINALS OF THE |
| TRANSFER |
| SWITCH TO BE WITHOUT ACCEPTABLE ELECTRICAL POWER. TABLE |
| 4.1(B) |
| PROVIDES THE TYPES DEFINED BY THIS STANDARD. |
| 4.4* LEVEL. THIS STANDARD RECOGNIZES TWO LEVELS OF |
| EQUIPMENT |
| INSTALLATION, PERFORMANCE, AND MAINTENANCE. |
| 4.4.1* LEVEL 1 SYSTEMS SHALL BE INSTALLED WHERE FAILURE |
| OF THE |
| EQUIPMENT TO PERFORM COULD RESULT IN LOSS OF HUMAN LIFE |
| OR |
| SERIOUS INJURIES. |
| 4.4.2* LEVEL 2 SYSTEMS SHALL BE INSTALLED WHERE FAILURE |
| OF THE |
| EPSS TO PERFORM IS LESS CRITICAL TO HUMAN LIFE AND |
| SAFETY. |
| 4.4.3 ALL EQUIPMENT SHALL BE PERMANENTLY INSTALLED. |
| 4.4.4* LEVEL 1 AND LEVEL 2 SYSTEMS SHALL ENSURE THAT |
| ALL LOADS |
| SERVED BY THE EPSS ARE SUPPLIED WITH ALTERNATE POWER |
| THAT |
| MEETS ALL THE FOLLOWING CRITERIA: |
| (1) OF A QUALITY WITHIN THE OPERATING LIMITS OF THE |
| LOAD |
| (2) FOR A DURATION SPECIFIED FOR THE CLASS AS DEFINED |
| IN TABLE |
| 4.1(A) |
| (3) WITHIN THE TIME SPECIFIED FOR THE TYPE AS DEFINED |
| IN TABLE |
| 4.1(B) |
| |
| PLEASE PROVIDE DETAILS AS THIS IS HOW IT WILL INSPECTED |
| AND THE ACCEPTANCE TESTING. |
| |
| |
| |
| |
| 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| |
| 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |