Plan Review Notes
Plan Review Notes For Permit 19060016
Permit Number 19060016
Review Stop B
Sequence Number 1
Notes
Date Text
2019-06-04 15:04:47****CORRECTIONS****
  
 SAMANTHA HILL / JONATHAN BROOKS
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FBC R 301, COMPLETE THE "SCHEDULE FOR INSTALLATION
 OF OPENING PROTECTIVE DEVICES" OR PROVIDE ALL
 INFORMATION REQUIRED IN ANOTHER FORMAT (SUCH AS EXCEL
 SPREADSHEET):
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS?PAGE=2
 2. WHEN COMPLETING THE INSTALLATION SCHEDULE, PLEASE
 NOTE PAGE 13 OF 20, FACTORS APPLY DEPENDING ON
 SUBSTRATE, EDGE DISTANCE AND FASTENER. FOR FASTENER, IF
 USING TAPCON, BE SPECIFIC AS TO WHICH TAPCON (TAPCON
 W/ADVANCED THREADFORM TECHNOLOGY REQUIRES A .9 FACTOR).
 3. REVISE PLAN TO SHOW MEANS OF ESCAPE REQUIRED BY FBC
 R 310.4; INCLUDE ROOM DESIGNATION
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved