2019-06-06 09:31:26 | ***CORRECTIONS*** | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | BUILDING PLAN REVIEW DENIED: | | | | 1. FBC B 107.2.1 A SURVEY IS REQUIRED WITH SET BACK | | MEASUREMENTS. | | 2. FBC R 311.2 THE SIZE OF DOOR (CLEAR WIDTH) NEEDS TO | | BE AT A MINIMUM OF 32". THE DOOR SCHEDULE INDICATES A | | DOOR WIDTH OF 30". | | 3. FBC B 107.2.1 THE RAMP FOOTING REINFORCEMENT DETAILS | | ARE REQUIRED. PLEASE PROVIDE DETAILS. | | 4. FBC B 107.2.1 THE RAMP FRAMING, DECKING, AND | | HANDRAIL CONNECTION AND FASTENER DETAILS ARE REQUIRED. | | PLEASE PROVIDE DETAILS. | | | | NOTE: A. THE WINDOW OPENING SIZE REQUIREMENTS FOR | | BEDROOM EGRESS MUST REMAIN IN PLACE AND CAN NOT BE | | COMPROMISED BY THE RAMP. | | B. THE ENTRY DOOR AND LANDING ORIENTATION MAY NEED TO | | BE ADJUSTED TO PROVIDE BETTER MANEUVERING CLEARANCE. | | |
|