Plan Review Notes
Plan Review Notes For Permit 19060008
Permit Number 19060008
Review Stop B
Sequence Number 1
Notes
Date Text
2019-06-06 09:31:26***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING PLAN REVIEW DENIED:
  
 1. FBC B 107.2.1 A SURVEY IS REQUIRED WITH SET BACK
 MEASUREMENTS.
 2. FBC R 311.2 THE SIZE OF DOOR (CLEAR WIDTH) NEEDS TO
 BE AT A MINIMUM OF 32". THE DOOR SCHEDULE INDICATES A
 DOOR WIDTH OF 30".
 3. FBC B 107.2.1 THE RAMP FOOTING REINFORCEMENT DETAILS
 ARE REQUIRED. PLEASE PROVIDE DETAILS.
 4. FBC B 107.2.1 THE RAMP FRAMING, DECKING, AND
 HANDRAIL CONNECTION AND FASTENER DETAILS ARE REQUIRED.
 PLEASE PROVIDE DETAILS.
  
 NOTE: A. THE WINDOW OPENING SIZE REQUIREMENTS FOR
 BEDROOM EGRESS MUST REMAIN IN PLACE AND CAN NOT BE
 COMPROMISED BY THE RAMP.
 B. THE ENTRY DOOR AND LANDING ORIENTATION MAY NEED TO
 BE ADJUSTED TO PROVIDE BETTER MANEUVERING CLEARANCE.
  