Plan Review Notes For Permit 19051589 |
Permit Number |
19051589 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-06-05 10:13:20 | 6/5/19 | | | | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1) SHEET 3 OF 7 - THE REVISED HEAD LOCATION COULD NOT | | BE IDENTIFIED PER THE APPLICATION LOCATION OR ANY OTHER | | PLAN SHEET. | | | | PER NFPA 1 | | | | 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION | | DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND | | SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE | | CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD | | CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS. | | | | PLEASE CLEARLY CLOUD OR OTHERWISE CLEARLY INDCIATE THE | | LOCATION. | | | | | | 2) SHEET 3 OF 7 - THE SPRINKLER LEGEND DOES NOT | | INDICATE THE ADDITION OF 2 NEW HEADS PER THE | | APPLICATION. | | | | 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION | | DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND | | SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE | | CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD | | CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS. | | | | PLEASE CLEARLY CLOUD OR OTHERWISE CLEARLY INDCIATE THE | | THE ADDITION OF TWO HEAD ON ALL APPLICABLE SHEETS. | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | | | | | |
|