Plan Review Notes
Plan Review Notes For Permit 19051589
Permit Number 19051589
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-06-05 10:13:206/5/19
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET 3 OF 7 - THE REVISED HEAD LOCATION COULD NOT
 BE IDENTIFIED PER THE APPLICATION LOCATION OR ANY OTHER
 PLAN SHEET.
  
 PER NFPA 1
  
 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION
 DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND
 SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE
 CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD
 CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS.
  
 PLEASE CLEARLY CLOUD OR OTHERWISE CLEARLY INDCIATE THE
 LOCATION.
  
  
 2) SHEET 3 OF 7 - THE SPRINKLER LEGEND DOES NOT
 INDICATE THE ADDITION OF 2 NEW HEADS PER THE
 APPLICATION.
  
 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION
 DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND
 SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE
 CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD
 CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS.
  
 PLEASE CLEARLY CLOUD OR OTHERWISE CLEARLY INDCIATE THE
 THE ADDITION OF TWO HEAD ON ALL APPLICABLE SHEETS.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  