Plan Review Notes
Plan Review Notes For Permit 19051536
Permit Number 19051536
Review Stop P
Sequence Number 2
Notes
Date Text
2019-08-22 16:01:55CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW
 PLUMBING COMMEMTS: DENIED
 1. SECOND REQUEST: SHOW OR PROVIDE NOTE THAT BOTH
 TOILET ROOM SINKS ARE TEMPERED 110F MAX BY AN ASSE 1070
 DEVICE. FBC P 607.1.2; NOTE THAT AFTER REVIEWING
 RESPONSE COMMENTS AND THE REVISED PLANS, I COULD NOT
 FIND EVIDENCE OF COMPLIANCE. PLEASE PROVIDE NOTE AND
 CLOUD AS A REVISION.
 2. FBC ACC 606.3 LAVATORIES AND SINKS SHALL BE
 INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR
 COUNTER SURFACE 34 INCHES (865 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND. DIMENSION ON COUNTER DETAIL
 SHALL BE TO THE FIXTURE RIM WHICH IS THE HIGHER OF THE
 TWO ITEMS.
 3. FOR A CLARIFICATION AND TO ALLOW FOR THE USE OF AN
 AIR ADMITTANCE VALVE FOR THE KITCHEN SINK AS OPPOSED TO
 PROVIDING A VENT THROUGH THE ROOF, PER WPB FBC 107.2.1,
 INDICATE ON THE PLAN VIEW THAT THE UPSTREAM SIDE OF THE
 BRANCH CONNECTION TO THE EXTERIOR DRAIN AS WELL AS 5
 FEET PLUS OR MINUS DOWNSTREAM OF THE BRANCH CONNECTION
 IS THE "SANITARY BUILDING DRAIN". PROVIDE AND SHOW A
 FULL SIZE TWO-WAY CLEANOUT TO GRADE AND DESIGNATE
 SANITARY BUILDING SEWER DOWNSTREAM OF THE CLEANOUT.
 ADDITIONALLY, INDICATE ON NOTE 1 ON P-1 "EXISTING
 BUILDING DRAIN" AS OPPOSED TO "EXISTING". ON THE
 SANITARY RISER DIAGRAMS ON P-2, TIE IN NOTES SHOULD SAY
 "EXISTING BUILDING DRAIN" AS OPPOSED TO "EXISTING".
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  