2019-06-28 15:33:461ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19051536
 6/28/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO SECTION 809.2 FBC EX AND PROVIDE MINIMUM
 VENTILATION CALCULATIONS FOR ALL ROOMS AND SPACES PER
 TABLE 403.3.1.1 FBC-17 MECHANICAL. PROVIDE A SCHEDULE
 THAT INDICATES THE REQUIRED AND PROVIDED CFMS OF
 OUTDOOR AIR.
  
 2) REFER TO SECTION 508.1.2 FBC EC AND PROVIDE AIR
 BALANCE CALCULATIONS.
  
 3) ADVISORY: SEPARATE PERMITS ARE REQUIRED FOR THE
 KITCHEN HOOD EXHAUST SYSTEM, AND FIRE SUPPRESSION
 SYSTEM. PLEASE NOTE THAT THE TEMPERATURE DIFFERENITAL
 BETWEEN MAKEUP AIR FOR THE HOOD AND AIR IN THE
 CONDITIONED SPACE SHALL NOT EXCEED 10 DEGREES F. THIS
 REQUIREMENT MAY AFFECT THE DESIGN OF THE MAIN HVAC
 SYSTEMS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  