Plan Review Notes
Plan Review Notes For Permit 19051536
Permit Number 19051536
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-06-13 11:56:31THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET A 2.0 - THERE IS AN INDICATION OF A GAS RANGE
 AND OVEN. WHERE FOOD IS PROCESSED THE INSTALLATION
 SHALL BE PROTECTION PER NFPA 101 AND OTHER APPLICABLE
 CODES.
  
 PER NFPA 101 CH 38 AND/OR 39 NEW & EXISTING BUSINESS
 OCCUOANCIES
  
 38.3.2.3* COMMERCIAL COOKING OPERATIONS. COMMERCIAL
 COOKING
 OPERATIONS SHALL BE PROTECTED IN ACCORDANCE WITH 9.2.3,
 UNLESS THE
 COOKING EQUIPMENT IS ONE OF THE FOLLOWING TYPES:
 (1) OUTDOOR EQUIPMENT
 (2) EQUIPMENT USED ONLY FOR FOOD WARMING
  
 39.3.2.3* COMMERCIAL COOKING OPERATIONS. COMMERCIAL
 COOKING OPERATIONS SHALL BE PROTECTED IN ACCORDANCE
 WITH 9.2.3,
 UNLESS THE COOKING EQUIPMENT IS ONE OF THE FOLLOWING
 TYPES:
 (1) OUTDOOR EQUIPMENT
 (2) EQUIPMENT USED ONLY FOR FOOD WARMING
  
  
 9.2.3 COMMERCIAL COOKING OPERATIONS. WHERE REQUIRED BY
 ANOTHER
 SECTION OF THIS CODE, COMMERCIAL COOKING OPERATIONS
 SHALL BE PROTECTED
 IN ACCORDANCE WITH NFPA 96, STANDARD FOR VENTILATION
 CONTROL AND
 FIRE PROTECTION OF COMMERCIAL COOKING OPERATIONS,
 UNLESS SUCH
 INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS,
 WHICH SHALL BE
 PERMITTED TO BE CONTINUED IN SERVICE.
  
 ANY PROPOSED INSTALLTION THAT INCLUDES A RANGE/STOVE
 TOP IN A COMMERCIAL/BUSINESS SETTING HAS THE POTENTIAL
 TO PRODUCE GREASE LADEN VAPORS AND SHALL BE PROTECTED
 FOR SUCH IN ACCORDNCE WITH NFPA 96 AND WITH A FIRE
 SUPPRESSION SYSTEM.
  
 EQUIPMENT DESIGN FOR WARMING; MICROWAVE, CONVECTION
 OVEN, TOASTER OVEN, ETC, WOULD NOT REQUIRE SUCH A
 SYSTEM.
  
 A HOOD AND FIRE SUPPRESSION SYSTEM SHALL BE INSTALLED
 UNDER SEPARATE PERMITS AND SHOP DRAWINGS.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGEMENT OR REMOVE THE GAS RANGE TOP.
  
  
  
 2) SHEET A 2.0 - THERE ARE HORIZONTAL SLIDING DOORS
 INDICATED IN THE MEAND OF EGRESS FROM THE CONFERNECE
 ROOM.
  
 PER NFPA 101
  
 38.2.2.2.7 HORIZONTAL OR VERTICAL SECURITY GRILLES OR
 DOORS
 COMPLYING WITH 7.2.1.4.1(3) SHALL BE PERMITTED TO BE
 USED AS PART
 OF THE REQUIRED MEANS OF EGRESS FROM A TENANT SPACE
  
 7.2.1.4 SWING AND FORCE TO OPEN.
 7.2.1.4.1* SWINGING-TYPE DOOR ASSEMBLY REQUIREMENT. ANY
 DOOR ASSEMBLY IN A MEANS OF EGRESS SHALL BE OF THE
 SIDE-HINGED OR
 PIVOTED-SWINGING TYPE, AND SHALL BE INSTALLED TO BE
 CAPABLE OF
 SWINGING FROM ANY POSITION TO THE FULL REQUIRED WIDTH
 OF THE
 OPENING IN WHICH IT IS INSTALLED, UNLESS OTHERWISE
 SPECIFIED AS
 FOLLOWS:
 (3) WHERE PERMITTED IN CHAPTERS 11 THROUGH 43,
 HORIZONTALSLIDING
 OR VERTICAL-ROLLING SECURITY GRILLES OR DOOR ASSEMBLIES
 THAT ARE PART OF THE REQUIRED MEANS OF EGRESS SHALL BE
 PERMITTED, PROVIDED THAT ALL OF THE FOLLOWING CRITERIA
 ARE MET:
 (A) SUCH GRILLES OR DOOR ASSEMBLIES SHALL REMAIN
 SECURED IN
 THE FULLY OPEN POSITION DURING THE PERIOD OF OCCUPANCY
 BY THE GENERAL PUBLIC.
 (B) ON OR ADJACENT TO THE GRILLE OR DOOR OPENING, THERE
 SHALL
 BE A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN
 1 IN. (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT
 READS AS FOLLOWS: THIS DOOR TO REMAIN OPEN
 WHEN THE SPACE IS OCCUPIED.
 (C) DOOR LEAVES OR GRILLES SHALL NOT BE BROUGHT TO THE
 CLOSED
 POSITION WHEN THE SPACE IS OCCUPIED.
 (D) DOOR LEAVES OR GRILLES SHALL BE OPERABLE FROM
 WITHIN THE
 SPACE WITHOUT THE USE OF ANY SPECIAL KNOWLEDGE OR
 EFFORT.
 (E) WHERE TWO OR MORE MEANS OF EGRESS ARE REQUIRED, NOT
 MORE THAN HALF OF THE MEANS OF EGRESS SHALL BE EQUIPPED
 WITH HORIZONTAL-SLIDING OR VERTICAL-ROLLING GRILLES OR
 DOOR
 ASSEMBLIES.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGEMENT OR CORRECT.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL