2019-06-13 11:56:31 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| |
| 1) SHEET A 2.0 - THERE IS AN INDICATION OF A GAS RANGE |
| AND OVEN. WHERE FOOD IS PROCESSED THE INSTALLATION |
| SHALL BE PROTECTION PER NFPA 101 AND OTHER APPLICABLE |
| CODES. |
| |
| PER NFPA 101 CH 38 AND/OR 39 NEW & EXISTING BUSINESS |
| OCCUOANCIES |
| |
| 38.3.2.3* COMMERCIAL COOKING OPERATIONS. COMMERCIAL |
| COOKING |
| OPERATIONS SHALL BE PROTECTED IN ACCORDANCE WITH 9.2.3, |
| UNLESS THE |
| COOKING EQUIPMENT IS ONE OF THE FOLLOWING TYPES: |
| (1) OUTDOOR EQUIPMENT |
| (2) EQUIPMENT USED ONLY FOR FOOD WARMING |
| |
| 39.3.2.3* COMMERCIAL COOKING OPERATIONS. COMMERCIAL |
| COOKING OPERATIONS SHALL BE PROTECTED IN ACCORDANCE |
| WITH 9.2.3, |
| UNLESS THE COOKING EQUIPMENT IS ONE OF THE FOLLOWING |
| TYPES: |
| (1) OUTDOOR EQUIPMENT |
| (2) EQUIPMENT USED ONLY FOR FOOD WARMING |
| |
| |
| 9.2.3 COMMERCIAL COOKING OPERATIONS. WHERE REQUIRED BY |
| ANOTHER |
| SECTION OF THIS CODE, COMMERCIAL COOKING OPERATIONS |
| SHALL BE PROTECTED |
| IN ACCORDANCE WITH NFPA 96, STANDARD FOR VENTILATION |
| CONTROL AND |
| FIRE PROTECTION OF COMMERCIAL COOKING OPERATIONS, |
| UNLESS SUCH |
| INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS, |
| WHICH SHALL BE |
| PERMITTED TO BE CONTINUED IN SERVICE. |
| |
| ANY PROPOSED INSTALLTION THAT INCLUDES A RANGE/STOVE |
| TOP IN A COMMERCIAL/BUSINESS SETTING HAS THE POTENTIAL |
| TO PRODUCE GREASE LADEN VAPORS AND SHALL BE PROTECTED |
| FOR SUCH IN ACCORDNCE WITH NFPA 96 AND WITH A FIRE |
| SUPPRESSION SYSTEM. |
| |
| EQUIPMENT DESIGN FOR WARMING; MICROWAVE, CONVECTION |
| OVEN, TOASTER OVEN, ETC, WOULD NOT REQUIRE SUCH A |
| SYSTEM. |
| |
| A HOOD AND FIRE SUPPRESSION SYSTEM SHALL BE INSTALLED |
| UNDER SEPARATE PERMITS AND SHOP DRAWINGS. |
| |
| PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF |
| ACKNOWLEDGEMENT OR REMOVE THE GAS RANGE TOP. |
| |
| |
| |
| 2) SHEET A 2.0 - THERE ARE HORIZONTAL SLIDING DOORS |
| INDICATED IN THE MEAND OF EGRESS FROM THE CONFERNECE |
| ROOM. |
| |
| PER NFPA 101 |
| |
| 38.2.2.2.7 HORIZONTAL OR VERTICAL SECURITY GRILLES OR |
| DOORS |
| COMPLYING WITH 7.2.1.4.1(3) SHALL BE PERMITTED TO BE |
| USED AS PART |
| OF THE REQUIRED MEANS OF EGRESS FROM A TENANT SPACE |
| |
| 7.2.1.4 SWING AND FORCE TO OPEN. |
| 7.2.1.4.1* SWINGING-TYPE DOOR ASSEMBLY REQUIREMENT. ANY |
| DOOR ASSEMBLY IN A MEANS OF EGRESS SHALL BE OF THE |
| SIDE-HINGED OR |
| PIVOTED-SWINGING TYPE, AND SHALL BE INSTALLED TO BE |
| CAPABLE OF |
| SWINGING FROM ANY POSITION TO THE FULL REQUIRED WIDTH |
| OF THE |
| OPENING IN WHICH IT IS INSTALLED, UNLESS OTHERWISE |
| SPECIFIED AS |
| FOLLOWS: |
| (3) WHERE PERMITTED IN CHAPTERS 11 THROUGH 43, |
| HORIZONTALSLIDING |
| OR VERTICAL-ROLLING SECURITY GRILLES OR DOOR ASSEMBLIES |
| THAT ARE PART OF THE REQUIRED MEANS OF EGRESS SHALL BE |
| PERMITTED, PROVIDED THAT ALL OF THE FOLLOWING CRITERIA |
| ARE MET: |
| (A) SUCH GRILLES OR DOOR ASSEMBLIES SHALL REMAIN |
| SECURED IN |
| THE FULLY OPEN POSITION DURING THE PERIOD OF OCCUPANCY |
| BY THE GENERAL PUBLIC. |
| (B) ON OR ADJACENT TO THE GRILLE OR DOOR OPENING, THERE |
| SHALL |
| BE A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS |
| THAN |
| 1 IN. (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT |
| READS AS FOLLOWS: THIS DOOR TO REMAIN OPEN |
| WHEN THE SPACE IS OCCUPIED. |
| (C) DOOR LEAVES OR GRILLES SHALL NOT BE BROUGHT TO THE |
| CLOSED |
| POSITION WHEN THE SPACE IS OCCUPIED. |
| (D) DOOR LEAVES OR GRILLES SHALL BE OPERABLE FROM |
| WITHIN THE |
| SPACE WITHOUT THE USE OF ANY SPECIAL KNOWLEDGE OR |
| EFFORT. |
| (E) WHERE TWO OR MORE MEANS OF EGRESS ARE REQUIRED, NOT |
| MORE THAN HALF OF THE MEANS OF EGRESS SHALL BE EQUIPPED |
| WITH HORIZONTAL-SLIDING OR VERTICAL-ROLLING GRILLES OR |
| DOOR |
| ASSEMBLIES. |
| |
| PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF |
| ACKNOWLEDGEMENT OR CORRECT. |
| |
| |
| 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |
| |
| |
| |