Plan Review Notes
Plan Review Notes For Permit 19051536
Permit Number 19051536
Review Stop E
Sequence Number 1
Notes
Date Text
2019-07-03 10:32:23FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 1) PLEASE SHOW DETAIL OF OUTLET AND LIGHTING CONTROL
 PER FBC ENERGY CODE
  
 2) ALL 120 VOLT 15 AND 20 AMPERE OUTLETS IN THE KITCHEN
 TO BE GFCI PROTECTED
  
 210.8(B) OTHER THAN DWELLING UNITS. ALL 125-VOLT,
 SINGLE-PHASE,
 15- AND 20-AMPERE RECEPTACLES INSTA LLED IN THE
 LOCATIONS SPECIFIED
 IN 210.8(B)(1) THROUGH (8) SHALL HAVE GROUND-FAULT
 CIRCUITINTERRUPTER
 PROTECTION FOR PERSONNEL. (2) KITCHENS