Text |
2019-06-18 11:38:33 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 19051536 |
| ADD: 201 ARKONA CT. |
| CONT: MIAMI SYSTEMS INC. |
| TEL: 561-394-5450 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION. |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. JUNE 17, 2019 |
| ACTION: DENIED |
| 1) PLEASE NOTE THE STATED VALUE FOR THIS PERMIT IS LOW |
| THE COST BREAKDOWN DOES NOT INCLUDE THE PROVISIONS FOR |
| THE SIDELIGHT GLASS OR SINGLE FRENCH DOOR (SHEET LS 1 |
| SHOWS DOUBLE DOORS AT THE FRONT ENTRY) NOR DOES THE |
| COST BREAK DOWN INCLUDE 22 NEW IMPACT WINDOWS OR THE |
| FEES FOR THE ARCHITECTURAL FIRM AND THE M-E-P ENGINEERS |
| OR THE STRUCTURAL ENGINEER. FOR PERMITTING PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| CONGRESS. |
| THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE |
| MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS. |
| WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING |
| PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE |
| QUALIFIER AND OWNER AND BRINGS IN THE LISTED |
| SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE |
| QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND |
| LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE |
| FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN |
| LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR |
| EACH PERMIT. |
| |
| ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK |
| STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE |
| AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS & |
| FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL |
| TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED |
| SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE, |
| LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR |
| FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE |
| REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT. |
| PLEASE PROVIDE A REVISED ITEMIZED LIST AND SUBTRACT |
| THESE LINE ITEMS AND THEIR VALUE FROM THE OVERALL |
| BUILDING VALUE STATED ON THE PERMIT APPLICATION FOR |
| THIS PROJECT. THE REMAINING BALANCE WILL BE AFFECTIVELY |
| THE VALUE OF THE BUILDING YOU WILL BE PAYING FOR THIS |
| PERMIT. THE BUILDING DEPARTMENT DOES NOT WANT TO |
| COLLECT TWICE FOR THE VALUE OF THESE SUB-PERMITS NOT |
| COVERED UNDER THE PRIME OR MASTER PERMIT. |
| 2A) THE STATED VALUE FOR THE PROJECT CURRENTLY IS |
| $336,000.00 DOLLARS IN VALUE, THIS WILL INCREASE. |
| PLEASE ALSO PROVIDE ON EITHER THE ARCHITECT?S OR |
| CONTRACTOR?S LETTER HEAD WHERE UP TO 0.20% OF THE |
| STATED VALUE OF THE PROJECT WILL BE SPENT ON MAKING |
| ACCESSIBLE UPGRADES TO THE BUILDING AND COMPLIANCE WITH |
| EITHER 202.4.1 DISPROPORTIONATE COST OR 202.4.2. |
| ACCESSIBLE FEATURES IN THE EVENT OF DISPROPORTIONATE |
| COST. |
| PLEASE LIST IN ORDER WHERE THE FUNDS WERE SPENT IN |
| ORDER TO MAKE THE PATH OF TRAVEL SHALL BE MADE |
| ACCESSIBLE THE PRIMARY FUNCTION AREA. 2017 |
| FBC-ACCESSIBILITY CODE. |
| |
| 2017 FBC-ACCESS. CODE 202.4.1 DISPROPORTIONATE COST. |
| ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF |
| TRAVEL TO THE ALTERED AREA WILL BE DEEMED |
| DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE |
| COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE |
| PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS |
| EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF |
| TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING |
| AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE |
| ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING |
| RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, |
| ENLARGING TOILET STALLS, INSULATING PIPES, OR |
| INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS |
| ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH |
| AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT, |
| INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT |
| TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING |
| AN INACCESSIBLE DRINKING FOUNTAIN. |
| |
| 3) SHEET X1 UNDER THE HEADING OF DESCRIPTION LIST |
| BOTTLED WATER IN LIEU OF HI-LO WALL MOUNT ADA DRINKING |
| FOUNTAINS. PLEASE REVIEW THE 2017 FBC-PLUMBING CODE |
| SECTION 410.2 DRINKING FOUNTAINS ARE NOT REQUIRED WHEN |
| THERE IS AN OCCUPANT LOAD OF 15 OR FEWER. WHEN THEY ARE |
| REQUIRED THEN COMPLIANCE WITH THE FBC-ACCESSIBILITY |
| CODE (2017) SECTION 211.2 IS REQUIRED. |
| |
| 2017 ACCESS. CODE 211.2 MINIMUM NUMBER. NO FEWER THAN |
| TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE DRINKING |
| FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH 602.6 AND ONE |
| DRINKING FOUNTAIN SHALL COMPLY WITH 602.7. |
| |
| 4) SHEET X1 UNDER THE HEADING OF PROJECT PLAN REVIEW |
| DATA MISSING INFORMATION NOT GIVEN IS THE BUILDING AND |
| OCCUPANT LOAD FACTOR (TABLE 1004.1.2. OF THE FBC-B) OR |
| OCCUPANT LOAD. |
| |
| 5A) THE LIFE SAFETY SHEET IN THE BOTTOM LEFT CORNER OF |
| THE PAGE INDICATES THE PLANS ARE DRAWN TO 1/8 INCH |
| SCALE, WHEREAS WHEN YOU SCALE THE PLAN, IT APPEARS TO |
| BE DRAWN TO ? INCH SCALE. TYPO, PLEASE CORRECT |
| THE DISCREPANCY. 107.2.1.2 ADDITIONAL INFORMATION IS |
| REQUIRED. APPEARS TO BE A TYPO. |
| |
| 5B) SHEET LS 1 INDICATES THE MAXIMUM ALLOWED TRAVEL |
| DISTANCE IS 100 FT. THIS IS ONLY TRUE WHEN THE TOTAL |
| OCCUPANT LOAD FOR THE BUILDING IS 100 FEET, AN OCCUPANT |
| LOAD OF 30 OR LESS THEN ONLY ONE EXIT IS REQUIRED. |
| THE OCCUPANT LOAD GIVEN IS 36 AND THE COMMON PATH OF |
| TRAVEL FROM THE OFFICE 104 ONE FOOT FROM THE WALL LINE |
| TO THE FRONT DOOR IS 82 FEET REQUIRING 2 MEANS OF |
| EGRESS FOR THIS BUILDING. SEE TABLE 1006.2.1 (FBC-B) |
| SPACES WITH ONE EXIT ACCESS DOORWAY. |
| |
| 5C) PEASE ALSO REVIEW SECTIONS: 2017 FBC-ACCESSIBILITY |
| CODE SECTION 207.1 MEANS OF EGRESS SHALL COMPLY WITH |
| SECTION 1003.2.13 OF THE INTERNATIONAL BUILDING CODE |
| (2000 EDITION AND 2001 SUPPLEMENT) OR SECTION 1007 OF |
| THE INTERNATIONAL BUILDING CODE (2003 EDITION). |
| |
| 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS |
| IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY |
| ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE |
| SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS. |
| PLEASE SHOW HOW BOTH THE FRONT AND REAR EXITS (EXIT |
| DISCHARGE) ARE GOING TO ALLOW THE OCCUPANTS TO TRAVEL |
| TO THE PUBLIC WAY. 2017 FBC-B 1028.5. PLEASE NOTE THIS |
| IS THE 1ST AREAS WHERE FUNDS ARE TO BE SPENT (I) COSTS |
| ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE AND AN |
| ACCESSIBLE ROUTE TO THE ALTERED AREA. |
| |
| 5D) THE LS1 SHEET IN THE BOTTOM LEFT CORNER OF THE |
| SHEET STATES THE GC IS TO PROVIDE PRICING FOR A 1 HOUR |
| FIRE BARRIER AT THE IT/ ELECTRIC PANEL ROOM 112, |
| CURRENTLY NOT SHOWN ON THE LS SHEET. PLEASE NOTE THERE |
| CANNOT BE ALTERNATES, THE PLANS HAVE TO BE SPECIFIC. |
| |
| 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION 107.2.1.3: W.P.B. |
| ADMINISTRATIVE CODE. 2017 DRAWINGS & SPECIFICATIONS |
| SHALL CONTAIN INFORMATION, IN THE FORM OF NOTES OR |
| OTHERWISE, AS TO THE QUALITY OF MATERIALS, WHERE |
| QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL |
| CODES. SUCH INFORMATION SHALL BE SPECIFIC TO THE |
| TECHNICAL CODES. CONSTRUCTION DOCUMENTS SHALL BE |
| SUFFICIENT CLARITY OF THE WORK PROPOSED AND SHOW IN |
| DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS |
| CODE AND RELEVANT LAWS, ORDINANCES, RULES AND |
| REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 5E) THE LIFE SAFETY SHEET INDICATES SEE SHEET E2 FOR |
| EMERGENCY LIGHTING. SHEET E2 IS MISSING BOTH EMERGENCY |
| LIGHTING IN THE OFFICE 114 AND A DIRECTIONAL SIGN, THE |
| ADA RESTROOM 113 HAS AN EMERGENCY LIGHT BUT THE ADA |
| BATHROOM 105 DOES NOT HAVE EMERGENCY LIGHTING, SHOW |
| COMPLIANCE WITH THE 2017 FBC-B SECTION 1013.1. SHEET |
| A2.0 SHOWS A FUTURE WALL SPLITTING OFFICE 114 INTO 2 |
| OFFICES ADDITIONAL DIRECTIONAL AND EMERGENCY LIGHTS |
| WILL ALSO BE NEEDED AT THAT TIME. |
| |
| 6) SHEET A1.0 DEMOLITION: |
| 6A) OLD OFFICE 107 NEW OFFICE 104 INDICATES NEW SAFE |
| ROOM, PROVIDE PRICE TO CUT FOOTER AND NEW BLOCK WALL, |
| IS THIS INCLUDED IN THE CONTRACT VALUE GIVEN? 107.2.1.2 |
| ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 6B) OLD OFFICE 107 NEW OFFICE 104 INDICATES NEW SAFE |
| ROOM SHEET A2.0 INDICATES WALL TYPE A WITH ADDED LAYERS |
| OF DRYWALL TO BE DETERMINED DURING CONSTRUCTION. NO |
| ALTERNATES ALLOWED, PLANS ARE TO BE SPECIFIC TO THE |
| TYPE OF CONSTRUCTION. ADMINISTRATION 107.2.1.3: W.P.B. |
| ADMINISTRATIVE CODE. 2017 DRAWINGS & SPECIFICATIONS |
| SHALL CONTAIN INFORMATION, IN THE FORM OF NOTES OR |
| OTHERWISE, AS TO THE QUALITY OF MATERIALS, WHERE |
| QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL |
| CODES. SUCH INFORMATION SHALL BE SPECIFIC TO THE |
| TECHNICAL CODES. |
| |
| 6C) SHEET A1.0 & SHEET A2.0. SHEET A2.0 THE FRONT ENTRY |
| SHOWS AN ALTERNATE TO CLEAN EXISTING PAVERS OR PRICE |
| FOR NEW PORCELAIN TILE. 2017 WEST PALM BEACH AMENDMENTS |
| TO THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| 107.2.1.3: W.P.B. ADMINISTRATIVE CODE. 2017 DRAWINGS & |
| SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO |
| THE TECHNICAL CODES. CONSTRUCTION DOCUMENTS SHALL BE |
| SUFFICIENT CLARITY OF THE WORK PROPOSED AND SHOW IN |
| DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS |
| CODE AND RELEVANT LAWS, ORDINANCES, RULES AND |
| REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 7) SHEET A2.0: |
| 7A) THE CONFERENCE ROOM (101) HAS 2 2 DOORWAYS WITH |
| SLIDING DOORS 101 & 106. THIS ROOM IS CONSIDERED A |
| SMALL ASSEMBLY SPACE AND MEETS THE REQUIREMENTS OF |
| FBC-B 303.1.2. THE ROOM IS 243 SQ. FT. / 15 = 17 |
| OCCUPANTS. THE 2017 FBC-B DOES NOT ALLOW FOR HORIZONTAL |
| SLIDING DOORS BE PART OF A MEANS OF EGRESS WHEN THERE |
| IS AN OCCUPANT LOAD MORE THAN 10 OCCUPANTS. SEE 2017 |
| FBC-B SECTION 1010.1.2 EXC. 9. |
| |
| 7B) PLEAS PROVIDE THE DIMENSIONS FOR THE NEW BENCH WITH |
| STORAGE BENEATH AND COMPLIANCE WITH THE 2017 |
| FBC-ACCESSIBILITY CODE SECTION 903.5 HEIGHT. THE TOP OF |
| THE BENCH SEAT SURFACE SHALL BE 17 INCHES (430 MM) |
| MINIMUM AND 19 INCHES (485 MM) MAXIMUM ABOVE THE FINISH |
| FLOOR OR GROUND |
| |
| 7C)(1) SHEET IT ROOM ALTERNATE PRICING AGAIN STATED. |
| 107.2.1.3: W.P.B. ADMINISTRATIVE CODE. 2017 DRAWINGS & |
| SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| TECHNICAL CODES. |
| |
| 7C)(2) THE PLAN STATES THE WALL TO BE 1 HOUR RATED. |
| SHEET A8.0 DETAIL 2 DOES DESIGNATE AN 1 HOUR FIRE RATED |
| ASSEMBLY, BUT DOES NOT PROVIDE THE REQUIRED COMPONENTS |
| FOR THE RATED ASSEMBLY. THE FIELD INSPECTOR WILL NEED |
| THESE FIRE RATED WALL ASSEMBLY COMPONENTS ON THE PLANS |
| TO COMPLETE THE FIELD INSPECTION. ADDITIONAL |
| INFORMATION IS REQUIRED. |
| |
| 7C)(3) IN THIS SAME DETAIL THE PLANS STATE THE |
| REQUIREMENT FOR THE 2003 IBC, 2004 & 2007 FBC-B PLEASE |
| UPDATE THE CODES AND CODE REFERENCES. THIS SAME DETAIL |
| ALSO REFERENCES THE REQUIREMENT FOR FIRE RESISTANT |
| JOINT SYSTEMS AROUND THE BAR JOIST AND ROOF DECK FLUTED |
| DECK SYSTEM, PLEASE PROVIDE COMPLIANCE WITH 2017 FBC-B |
| SECTION 715.1. |
| |
| 7D) RECEPTION AREA DESK PASS THROUGH INDICATES FINAL |
| HEIGHT TO BE DETERMINED IN INTERIOR DESIGN DRAWINGS. |
| MUST COMPLY WITH THE 2017 FBC-ACCESS. CODE SECTIONS: |
| |
| 904.3.3 CHECK WRITING SURFACES. WHERE PROVIDED, CHECK |
| WRITING SURFACES SHALL COMPLY WITH 902.3. |
| |
| 904.4 SALES AND SERVICE COUNTERS. SALES COUNTERS AND |
| SERVICE COUNTERS SHALL COMPLY WITH 904.4.1 OR 904.4.2. |
| THE ACCESSIBLE PORTION OF THE COUNTER TOP SHALL EXTEND |
| THE SAME DEPTH AS THE SALES OR SERVICE COUNTER TOP. |
| |
| 7E) OFFICE 104 SHOWS AN EGRESS WINDOW, WILL THIS OFFICE |
| BE USED AS A SLEEPING ROOM REQUIRING AN EGRESS WINDOW? |
| IF SO PLEASE PROVIDE THE STYLE OF WINDOW, SIZE OF |
| WINDOW, THE WINDOW SCHEDULE ON SHEET A9.0 JUST STATES |
| MATCH EXISTING. PROVIDE COMPLIANCE WITH ALL SECTIONS OF |
| 1030.2 & 1020.3 OF THE 2017 FBC-B. |
| |
| 7F) OFFICES 102 & 103 ALTERNATE PRICING FOR GLAZING. |
| 107.2.1.3: W.P.B. ADMINISTRATIVE CODE. 2017 DRAWINGS & |
| SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| TECHNICAL CODES. |
| |
| 7G) THE BREAK ROOM 108 REFERENCES THE INSTALLATION OF A |
| MICROWAVE OVER THE OVEN PLEASE NOTE THERE IS NO |
| ELEVATIONS FOR THE PLACEMENT OF THE MICROWAVE BUT WILL |
| NEED TO SHOW COMPLIANCE WITH THE 2017 ACCESS. CODE |
| SECTIONS: |
| 308 REACH RANGES |
| 308.2 FORWARD REACH. / 308.2.1 UNOBSTRUCTED/ 308.2.2 |
| OBSTRUCTED HIGH REACH. |
| 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 |
| OBSTRUCTED HIGH REACH. |
| |
| 309 OPERABLE PARTS |
| 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN ONE |
| OR MORE OF THE REACH RANGES SPECIFIED IN 308. |
| 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE WITH |
| ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING, |
| PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED |
| TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS |
| MAXIMUM. |
| |
| 8) SHEET A4.0: |
| 8A) THE ADA BATHROOM # 105 SHOWS THE WATERCLOSET?S |
| CLEAR FLOOR SPACE BEING INTERFERED WITH THE LAVATORY |
| VANITY WITHIN THE REQUIRED 60 INCH CLEAR FLOOR SPACE |
| REQUIRED FOR THE WATERCLOSET. SEE THE 2017 FBC-ACCESS. |
| CODE 604.3.1 & 604.3.2. |
| |
| 8B) DETAILS 2, 3 & 4 BOTH SHOW THE GRAB BARS AT A |
| HEIGHT OF 3 FEET TO THE CENTER OF THE GRAB BAR. PLEASE |
| NOTE A CODE CHANGE AS HOW YOU MEASURE THE HEIGHT, TO |
| THE TOP OF THE GRASPING SURFACE, NOT CENTER LINED. SEE |
| |
| 2017 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF |
| GRAB BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL |
| POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE |
| THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING |
| SURFACE, NOT CENTERLINE. |
| |
| 8C) THE PLUMBING SCHEDULE DOES INDICATE THE |
| INSTALLATION OF ADA MIRRORS BUT NONE OF THE DETAILS |
| SHOW THE ACTUAL HEIGHT THE MIRRORS ARE TO BE INSTALLED. |
| PLEASE SHOW COMPLIANCE WITH THE 2017 ACCESS. CODE 603.3 |
| MIRRORS. MIRRORS LOCATED ABOVE LAVATORIES OR |
| COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF |
| THE REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE |
| FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE |
| LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE |
| BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES MAXIMUM |
| ABOVE THE FINISH FLOOR OR GROUND. |
| |
| 8D) PLEASE REVIEW DETAIL # 2 IN REGARDS TO THE TOP OF |
| THE VANITY WHERE THE UNDER MOUNT LAVATORY IS INSTALLED, |
| THE HEIGHT OF THE VANITY IS NOT GIVEN. SHOW COMPLIANCE |
| WITH THE 2017 ACCESS. CODE SECTION 606.3 HEIGHT. |
| LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT |
| OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES |
| MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| |
| 8E) THE DETAILS DO NOT PROVIDE THE LOCATION OF THE |
| TOILET PAPER DISPENSER LOCATION. SHOW COMPLIANCE WITH |
| 2017 ACCESS. CODE 604.7 DISPENSERS. TOILET PAPER |
| DISPENSERS SHALL COMPLY WITH 309.4 AND SHALL BE 7 |
| INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT OF THE |
| WATER CLOSET MEASURED TO THE CENTERLINE OF THE |
| DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15 |
| INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH |
| FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS. |
| DISPENSERS SHALL NOT BE OF A TYPE THAT CONTROLS |
| DELIVERY OR THAT DOES NOT ALLOW CONTINUOUS PAPER FLOW. |
| |
| 9) SHEET S1.0: |
| 9A) UNDER THE HEADING OF WIND LOADS (J) THE PLANS |
| INDICATE THE BUILDING IS LOCATED WITHIN THE HIGH |
| VELOCITY HURRICANE ZONE AND THE WINDS SHOWN ALSO |
| REFLECT AS SUCH. IF THE DESIGNER OF RECORD WISHES TO |
| DESIGN TO THE HIGHER WIND ZONE YOU MAY BUT PLEASE |
| REMOVE THE WORDING HIGH VELOCITY HURRICANE ZONE, THAT |
| IS FOR BROWARD AND MIAMI-DADE COUNTIES ONLY. |
| |
| 9B) WALL PRESSURE CHART/ COMPONENTS AND CLADDING CHART. |
| THE CHART DOES NOT PROVIDE IF THE GIVEN PRESSURES ARE |
| IN VASD OR VULT. IT WOULD APPEAR THE PRESSURES ARE IN |
| VASD PLEASE INDICATE AS SUCH. NOTE ALL PRODUCT |
| APPROVALS ARE IN VASD WHICH HELPS IN CHECKING |
| PRESSURES. 107.2.1.2 ADDITIONAL INFORMATION IS |
| REQUIRED. |
| |
| 9C) NO ROOF PRESSURES ARE GIVEN, THE DEMOLITION SHEET |
| AND A2.1 INDICATES THERE WILL BE ROOF REPAIRS NEEDED |
| AND SO THE PRESSURES FOR ROOF ZONES 1, 2 & 3 WILL BE |
| REQUIRE. 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 9D) COMPONENTS & CLADDING. 2017 FBC-B 1609.1.2 |
| PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS, & MULLIONS. |
| (B) WINDOWS & MULLIONS |
| (C) PANEL WALLS: WALL LOUVERS |
| (D) ROOFING PRODUCTS AND ASSEMBLIES, |
| |
| 9E) IDENTIFY GLAZING/ MULLIONS. |
| PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE |
| SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION |
| TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH |
| GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, |
| TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED |
| OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B |
| 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S |
| INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| |
| 9F) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE |
| PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| |
| 9G) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| FOR REVIEW BY THE BUILDING OFFICIAL. |
| |
| DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| OFFICIAL. |
| |
| 9H) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY |
| ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES |
| FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL |
| LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF |
| ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR |
| BOTH INSULATION & THE BASE SHEET AS CALCULATED IN |
| COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117. |
| CALCULATION PREPARED, SIGNED AND |
| SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR |
| REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS & |
| CLADDING. |
| |
| 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| |
| |