2022-04-19 13:25:49 | 2ND REVIEW FBC-2020 PLUMBING |
| PERMIT- 19051525 |
| 4/19/2022 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| PREVIOUS REVIEW ARE LISTED BELOW TITH ADDITIONAL NOTES |
| FOR CLARIFICATION. |
| |
| 4) FAILED. P101 & P301: SHOW THE HWR LINE ON THE |
| PLUMBING FLOOR PLAN AND IN THE ISOMETRIC DRAWING- |
| SECTION 607.2 FBC P, AND C404.5.1 FBC EC. THE 1/2-INCH |
| HW WATER LINES TO THE LAVATORIES ARE EXCEEDING THE |
| MAXIMUM LENGTHS OF 2 FT FROM THE HOT WATER SOURCE TO |
| THE FIXTURE- REFER TO SECS. C404.5.1 & C404.5.2 FBC EC. |
| |
| 6C) FAILED. P102: PROVIDE PRIMARY AND EMERGENCY SCUPPER |
| AND DOWN SPOUT SIZES- TABLE 1106.3 & SECS.1106.5, |
| 1108.1 FBC P. PLEASE INCLUDE CONSTRUCTION DETAILS OR |
| INSTALLATION DETAILS FOR MANUFACTURED PRODUCTS- SEC. |
| 107.2.1 WPB. SCUPPPER DETAILS NOT PROVIDED. PLEASE SEE |
| SECS. 1503.4.2 & 1503.4.2.1 FBC B. |
| |
| NEW COMMENT. |
| |
| 1) INDICATE HOW TEMPERED WATER WILL BE DELIVERED FROM |
| THE LAVATORIES- SEC. 419.5 FBC P. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |